Fujitsu Wall Mounted Type Installationshandbuch - Seite 4
Blättern Sie online oder laden Sie pdf Installationshandbuch für Klimagerät Fujitsu Wall Mounted Type herunter. Fujitsu Wall Mounted Type 18 Seiten. Air conditioner outdoor unit, wall mounted type, r410a
2.4. Accessories
The following installation accessories are supplied. Use them
as required.
Name and Shape
Operating Manual
Installation Manual
(This manual)
Wall hook bracket
Remote
controller
Battery
Remote
controller
holder
The following items are necessary to install this air condi-
tioner. (The items are not included with the air conditioner
and must be purchased separately.)
Name
Connection pipe assembly
Connection cable (4-conductor)
Wall pipe
Decorative tape
Vinyl tape
Wall cap
Saddle
Drain hose
Tapping screws
Sealant
M10 bolt, nut
En-4
Q'ty
Name and Shape
Q'ty
Drain hose insulation
1
1
Cloth tape
1
1
Tapping screw (big)
1
8
Tapping screw
(small)
1
2
Air cleaning filter
2
2
Air cleaning filter
frame
1
2
Q'ty
1
1
1
1
1
1
1 set
1
1 set
1
4 set
1
2.5. Optional parts
Refer to each installation manual for the method of installing
optional parts.
Parts name
Model No.
Wired Remote
UTY-
Controller
RNNUM
Wireless Remote
UTY-
Controller
LNHUM
Simple Remote
UTY-
Controller
RSNUM
External connect
UTY-
kit
XWZX
3. GENERAL
This INSTALLATION MANUAL briefly outlines where and how to
install the air conditioning system. Please read over the entire set of
instructions for the indoor and outdoor units and make sure all ac-
cessory parts listed are with the system before beginning.
] 1
3.1. Type of copper pipe and insulation material
CAUTION
Refer to the installation manual for the outdoor unit for
description of allowable pipe length and height difference.
3.1.1. SINGLE TYPE INSTALLATION
MODEL
Liquid pipe
18,000BTU/h model
9.52mm (3/8in.)* 15.88mm (5/8in.)*
24,000BTU/h model
9.52mm (3/8in.)* 15.88mm (5/8in.)
* When single type installation, the ADAPTER included outdoor
unit is necessary to connect the indoor unit to the outdoor unit.
3.1.2. MULTI TYPE INSTALLATION
MODEL
Liquid pipe
18,000BTU/h model
6.35mm (1/4in.)
24,000BTU/h model
6.35mm (1/4in.)
CAUTION
Install heat insulation around both the gas and liquid pipes.
Failure to do so may cause water leaks.
Use heat insulation with heat resistance above 248 °F.
Reverse cycle model only
In addition, if the humidity level at the installation location
of the refrigerant piping is expected to exceed 70%, install
heat insulation around the refrigerant piping. If the expected
humidity level is 70-80%, use heat insulation that is 15 mm
(19/32 in.) or thicker and if the expected humidity exceeds
80%, use heat insulation that is 20 mm (25/32 in.) or thicker.
If heat insulation is used that is not as thick as specifi ed,
condensation may form on the surface of the insulation.
In addition, use heat insulation with heat conductivity of
0.045 W/(m•K) or less (at 68 °F).
] 1
3.2. Additional materials required for installation
A. Refrigeration (armored) tape
B. I n s u l a t e d s t a p l e s o r c l a m p s f o r c o n n e c t i n g w i r e
(See your local electrical codes.)
C. Putty
D. Refrigeration lubricant
E. Clamps or saddles to secure refrigerant piping
Application
For air conditioner
operation
For air conditioner
operation
For air conditioner
operation
For control input/output
port
Diameter
Gas pipe
Diameter
Gas pipe
12.70mm (1/2in.)
15.88mm (5/8in.)