Recommended t-Stat Wire length
thermostat
Wire Gauge
2-Wire
(Heating)
24
22
20
18
table 2. thermostat Wire Gauge
Refer to the thermostat's instruction sheet for detailed
mounting and installation information.

Defrost cycle timer

The defrost cycle timer controls the time interval of the hot
gas defrost after the defrost sensor closes. It is located
in the lower left corner of the defrost control board on the
low voltage side of the control box. Three interval settings
are available: 30 minutes, 60 minutes, and 90 minutes.
Time setting selection is dependent on the climate where
the unit is being installed.
• Example 1: Dry climate of Southern Arizona - A 90
minute setting is recommended.
• Example 2: Moist climate of Seattle, Washington - A 30
minute setting is recommended.
To set the cycle timer, place the timing pin on the defrost
control board to the desired time interval post. notE: All
units are shipped from the factory with the default time
setting of 30 minutes.

Demand Defrost control

The demand defrost board controls the defrost cycle
in response to ambient temperature, outdoor coil
temperature and accumulated compressor run time. The
heat pump is allowed to operate in the heating mode
until the combination of outdoor ambient and outdoor
coil temperatures indicate that defrosting is necessary,
based on the programmed defrost curve. There are four
preprogrammed defrost curves on the board.
• A jumper pin is used to switch between the different
curves. The default jumper position is curve 1 and is the
recommended setting for most standard applications.
See
Table 3
for additional defrost curves settings.
• The factory default setting does not include a 30 second
compressor delay function and has a 40° F defrost
terminate temperature. If additional defrost time is
needed, a higher terminate temperature is available
by selecting a different demand curve. notE: The 30
second compressor delay function is optional and based
on the demand curve selected.
10
(Unit to t-Stat)
5-Wire
(Heating/cooling)
55
25
90
45
140
70
225
110
• The standard defrost cycle will terminate after 13 minutes
and 39 seconds or when the coil temperature reaches
its terminate temperature, whichever occurs first.
• The defrost board is equipped with a 5 minute Anti-Short
Cycle Delay (ASCD). The compressor will not turn on
until it reaches the minimum 5 minute off time.
• The control contains a forced - defrost feature, which
places the system into defrost mode every 6 hours and
4 minutes, unless the coil temperature is above the
selected terminate temperature.
• The system can be manually forced into defrost mode at
any time by shorting the tESt terminals on the demand
defrost board together for more than 9 seconds. The
coil temperature sensor does not need to be cold when
the unit is forced into defrost. After the tESt input is
removed, the defrost mode will terminate in 13.7 minutes,
if the coil temperature is above the terminate set-point,
or when the Y input is removed, whichever occurs first.
notE: If a demand curve is selected which has a 30
second compressor time delay in defrost, the delay is
reduced to 10 seconds in TEST mode.

optional outdoor thermostat

An outdoor thermostat can be installed in the field with
2-stage electric heat by removing the orange wire from
the E terminal on the terminal block and connecting to the
outdoor thermostat. Connect the other side of the outdoor
thermostat to W2 from the thermostat.

optional Electric Heater Kits

Optional electric heater kits are available in 5 kw through
20 kw heating capacities. Single package heat pumps
are designed to allow optional electric heat to be field
installed as required by the building's particular heating
load. The options available for each unit are shown in the
heater kit installation instructions. A heating/cooling 24V
thermostat should be used when an electric heater kit is
installed. notE: A 2-stage heating thermostat is required
if installing a 2-stage heater kit. As previously noted, a
field installed circuit breaker kit is available as a means
of electrical disconnect for the unit. Install the heater kits
as directed by the instructions supplied with the heater
kit. Follow all cautions and warnings as directed.
MInIMUM tIME
jUMPER
BEtWEEn
PoSItIon
DEFRoStS (MIn)
1
20
2
20
3
20
4
20
table 3. Demand Defrost curve Profiles
tERMInAtE
30 SEconD
tEMPERAtURE
coMPRESSoR
(° F)
DElAY FUnctIon
40
no
40
YES
75
NO
75
YES