Kohler 6EF Operation - Seite 17
Blättern Sie online oder laden Sie pdf Operation für Motor Kohler 6EF herunter. Kohler 6EF 48 Seiten. Marine generator sets
2.6.2
Starting the Generator Set
The following table describes the actions required to
start the generator set.
WARNING
Explosion.
Gasoline
vapors
explosion and severe injury or
death.
Before starting the generator set,
operate the blower 4 minutes and
check the engine compartment for
gasoline vapors.
Step
Step
1
Operate the blower.
Operate the blower 4 minutes and check the engine
compartment for gasoline vapors.
2
Fuel shut-off valve.
Open the manual fuel shut-off valve, if equipped.
3
Starting.
Place the generator set controller start/stop switch
or the remote start/stop switch in the START
position.
TP-5985 10/02
can
cause
Action
Action
2.6.3
Remote Panel Gauge Operation
If the generator set has an optional remote panel with
gauges, observe the gauges upon engine start-up. If
gauge readings are not within the ranges specified,
contact an authorized service distributor/dealer.
Gauge
Oil pressure
Water temperature
DC voltmeter
*50 Hz models show a slightly lower pressure range.
2.6.4
Stopping the Generator Set
The following table describes the actions required to
stop the generator set.
Step
Step
1
Cooldown
Run generator set at no load for 5 minutes to ensure
adequate engine cooldown.
2
Stopping
Place controller start/stop switch or remote
start/stop switch in the stop position and wait until
the generator set comes to a complete stop.
3
Fuel shut-off valve
Close the manual fuel shut-off valve, if equipped.
Normal Operating Range
276-414 kPa (40-60 psi)*
°
°
91-104
C (195-219
F)
12-14 volts
Action
Action
Section 2 Operation