Kohler 10RESV Installationshandbuch - Seite 25
Blättern Sie online oder laden Sie pdf Installationshandbuch für Tragbarer Generator Kohler 10RESV herunter. Kohler 10RESV 48 Seiten. Residential/commercial generator sets
Auch für Kohler 10RESV: Einbauanleitung (2 seiten)
1.10.3 System Connections with
Accessory Modules
See Figure 1-24 through Figure 1-26 for connection
options with accessory modules. Accessory modules
can include one Model RXT transfer switch, one
Generator Set
Note: See Section 1.10.2, Cable Specifications for
maximum cable lengths.
* RXT transfer switch with standard or combined interface/load
management board. Do not use a load shed kit with a
combined interface board.
1. Customer connection terminal block. See Figure 1-18 for location. Check the decal on the generator set for terminal block connections.
2. Connect one end of each cable shield to GROUND at the generator set.
3. See Figure 1-22 for cable specifications, including maximum total cable length per run (1 run shown).
4. Connect shields together as shown.
5. Leave the end of each cable shield disconnected at the last device.
Figure 1-23 Accessory Module Communication Connection Details
TP-6984
5/17a
1
GND
3
4
COM
COM
12 VDC
PWR
PWR
B
B
RBUS
A
A
TB3
programmable interface module (PIM) and one load
shed kit.
See Figure 1-22 for the maximum total cable length with
1, 2, or 3 accessory modules per cable run.
2
3
A
B
PWR
COM
4
A
B
PWR
COM
A
B
PWR
COM
5
A
B
PWR
COM
5
Load Shed Kit
RXT*
A
B
PWR
COM
PIM
Section 1 Installation
25