Kohler 14/20RESL Betriebshandbuch - Seite 17

Blättern Sie online oder laden Sie pdf Betriebshandbuch für Tragbarer Generator Kohler 14/20RESL herunter. Kohler 14/20RESL 48 Seiten. Residential/commercial generator sets

Kohler 14/20RESL Betriebshandbuch

2.1 Prestart Checklist

To ensure continued satisfactory operation, perform the
following checks or inspections before or at each
startup, as designated, and at the intervals specified in
the service schedule. In addition, some checks require
verification after the unit starts.
Air Cleaner. Check for a clean and installed air cleaner
element to prevent unfiltered air from entering the
engine.
Air Inlets. Check for clean and unobstructed air inlets.
Battery. Check for tight battery connections. Consult
the battery manufacturer's instructions regarding
battery care and maintenance.
Exhaust System.
Check for exhaust leaks and
blockages. Check the muffler condition.
D
Inspect the exhaust system components for cracks,
leaks, and corrosion. Check for tight exhaust system
connections.
D
Check for corroded or broken metal parts and replace
them as needed.
D
Check that the exhaust outlet is unobstructed.
Oil Level.
Check the oil level before starting the
generator set and at the intervals given in Section 3,
Scheduled Maintenance. Maintain the oil level at or
near, not over, the full mark on the dipstick.
Operating Area. Check for obstructions that could
block the flow of cooling air. Keep the air intake area
clean. Do not leave rags, tools, or debris on or near the
generator set.

2.2 Exercising the Generator Set

Operate the generator set without load once each week
for 20 minutes. If the generator set is connected to a
Kohlerr model RRT transfer switch, a weekly ultra-quiet
diagnostic test/exercise can be set to run automatically.
See Section 2.7 for instructions to set the exerciser.
If the generator set is connected to a Kohlerr model
RDT or RSB transfer switch, refer to the transfer switch
instructions to set the automatic exercise function. If the
generator set is not connected to an automatic transfer
switch (ATS) with an exercise option, run the unit in the
presence of an operator.
TP-6734 5/10

Section 2 Operation

The operator should perform all of the prestart checks
before starting the exercise procedure.
generator set according to the starting procedure in the
controller section of this manual. While the generator
set is operating, listen for a smooth-running engine and
visually inspect the generator set for fluid or exhaust
leaks. Check the air inlets and outlets and remove any
items restricting the air flow.
2.3 RDC and DC Generator Set/
Transfer Switch Controllers
RES model generator sets are equipped with the
Residential Digital Control (RDC). The RDC controls
the power system generator set and model RRT
automatic transfer switch (ATS) (if equipped).
controller receives voltage sensing data from the ATS
and operates the generator set and transfer switch to
provide standby power when utility power is lost.
If the generator set is not connected to a Kohlerr model
RRT ATS, the RDC/DC controller functions as a
generator set controller only. ATS communication and
functions do not operate with other ATS models. The
ultra-quiet diagnostic test/exercise is not available with
other ATS models.

2.4 Controller Power

The RDC and DC controllers are powered by the
generator set engine starting battery.
Note: The generator sets are equipped with factory-
installed battery chargers to prevent battery
discharge.
The battery charger must be
connected to utility power.
Start the
The
Section 2 Operation
17