Kohler 20RCA Bedienungsanleitung für Installation und Betrieb
Blättern Sie online oder laden Sie pdf Bedienungsanleitung für Installation und Betrieb für Tragbarer Generator Kohler 20RCA herunter. Kohler 20RCA 37 Seiten.
INSTALLATION AND OPERATION INSTRUCTIONS
Original Issue Date: 8/12
Model: 14RESA, 20RESA, 20RESB, 20RESC, 20RESD, 14RCA and 20RCA
Market: Residential/Light Commercial
Subject: PowerSyncr Automatic Paralleling Module (APM) Kit
Introduction
This document describes the installation and operation
of the PowerSyncr Automatic Paralleling Module (APM)
and optional circuit breakers for single-phase residential
generator sets. The APM allows the use of two Model
14RESA, two 14RCA, two 20RESA/B/C/D, or two
20RCA generator sets in a single-phase paralleling
system to supply power to one building or site.
The APM provides a common connection point for
paralleling generators and permits individual control of
the
generator
connections,
synchronization,
redundancy,
management.
The APM and associated equipment must be installed
by a Kohlerr trained and authorized distributor or dealer.
Figure 1 PowerSyncr Automatic Paralleling Module
GM85144-KP1-QS and Circuit Breaker Kits GM86368-KP1-QS and
GM86369-KP1-QS
allowing
and
generator
zab26291
The following combinations of single-phase
generator sets can be paralleled:
Two single-phase model 14RESA or 14RCA
D
generator sets with the same 110/220, 115/230,
120/240, 220, 230, or 240 volt configuration
Two single-phase model 20RESA/B/C/D or 20RCA
D
generator sets (must have the same 110/220,
115/230, 120/240, 220, 230 or 240 volt configuration)
Automatic paralleling requires:
Two single-phase generator sets as shown above.
for
D
RDC2 controllers with blue circuit boards. If the
D
generator has a controller with a green or red circuit
board, replace it with a blue board controller.
Paralleling firmware APM RDC2 version 210.0.0 or
D
higher on each generator controller. Download the
paralleling firmware from the Service Support section
on KPRC.
Note: Contact the Residential Service Department
for assistance if the controllers have an
older version (e.g. 101.0.3) of paralleling
firmware.
One Automatic Paralleling Module (APM) kit
D
One Model RXT automatic transfer switch (ATS)
D
A load management device* is required if one
D
generator set cannot support the maximum total load.
A
personal
D
SiteTecht software version 3.5 or higher is required
for system setup.
A load management device* is necessary in order to
shed non-critical loads in the event that one generator
set shuts down and the other generator set cannot
support all of the loads.
* A load management device is a load control module (LCM), load
shed kit, or combined interface/ load management board on the
RXT ATS.
TT-1596 8/22g
computer
(laptop)
with
Kohlerr