Kohler 30RES Handbuch - Seite 31
Blättern Sie online oder laden Sie pdf Handbuch für Tragbarer Generator Kohler 30RES herunter. Kohler 30RES 36 Seiten. Residential generator sets
4.5 Controller Troubleshooting
Figure 4-3 contains troubleshooting information for the
Advanced Digital Control.
Problem
Possible Cause
Controller LED
No power to the controller:
display is off.
Controller powers down if the generator set
has not run for 48 hours or longer.
Controller fuse (F3) is blown.
Low or no battery voltage.
Generator set master switch is in the
OFF/RESET position.
Figure 4-3 ADC 2100 Troubleshooting Chart
TP-6344 4/09
Corrective Action
Controller display will automatically activate when a
remote start command is received or the generator
set master switch is moved to the RUN position.
Replace the fuse. See Figure 4-1. If the fuse blows
again, contact an authorized Kohler distributor/
dealer.
Check connections.
Check generator set battery. See Figure 4-2.
Move generator set master switch to the AUTO or
RUN position.
Section 4 Troubleshooting
31