Kohler 36VDC Installationsanleitung Handbuch - Seite 17

Blättern Sie online oder laden Sie pdf Installationsanleitung Handbuch für Tragbarer Generator Kohler 36VDC herunter. Kohler 36VDC 44 Seiten. Dc generator sets

Kohler 36VDC Installationsanleitung Handbuch
1.8.4

Power Supply

Provide AC power for the battery charger (integral to
the VSC controller) and optional carburetor heater.
The power requirements are shown in Figure 1-10.
The power source must be GFCI protected.
power to the accessories must be available at all
times, i.e. the circuit must be powered by the primary
source and backed up by the generator.
Be sure to disconnect power at the distribution panel
before making the connections. Connect power leads
to the utility power connection points on the terminal
block shown in Figure 1-9. See Section 1.8.3 and the
wiring diagrams in Section 2 for connection details.
Figure 1-10
Equipment
Watts
Battery charger
(standard, integral to
VSC controller)
Carburetor heater
(optional)
Figure 1-10 Power Requirements
1.8.5
Programmable Interface Module
(PIM) Connection
One
programmable
connected to the generator set. Route low-voltage
communication leads through separate conduit. All
Figure 1-12
Generator Set
Note: Check the decal on the generator set for terminal block connections.
1. Connect one end of each cable shield to GROUND at the generator set.
2. Communication cable Belden #9402 or equivalent 20 AWG shielded, twisted-pair cable
3. Leave one end of each cable shield disconnected.
Figure 1-12 Programmable Interface Module (PIM) Communication Connection to Generator Set Terminal Block
TP-6842 7/15
Power Requirement, Max.
Amps
Volts
120
1
100-250 VAC
50/60 Hz
37
0.33
120 VAC
50/60 Hz
interface
module
can
GND
3
4
COM
COM
12 VDC
PWR
PWR
B
RBUS
A
1
1A
OPEN
OPEN
TB2
connections must comply with applicable state and
local codes.
See Figure 1-12. Use Belden #9402 or equivalent
20 AWG shielded, twisted-pair cable to connect P10-1
The
through P10-4 on the programmable interface module
(PIM) to the generator set terminal block TB1
connections A, B, PWR, and COM. Note the shield
connections shown in Figure 1-12.
cable length using Belden #9402 cable is 61 m
(200 ft.).
For longer cable runs, use Belden #8762 or equivalent
20 AWG shielded, twisted-pair cable with 2 conductors
for the A and B connections, and use 12-14 AWG wire
for the COM and PWR connections. See Figure 1-11
for the maximum cable lengths.
Figure 1-11
PWR and COM Connections
Belden #9402 or equivalent 20AWG
14 AWG
12 AWG
Figure 1-11 Maximum Cable Lengths
be
1
B
A
2
Cable
Maximum length
3
Programmable Interface
Module (PIM)
A
B
PWR
COM
3
Section 1 Installation
The maximum
meters (ft.)
61 (200)
152 (500)
152 (500)
PIM
KPS_067
17