Kohler GM93357-KP2 Einbauanleitung

Blättern Sie online oder laden Sie pdf Einbauanleitung für Tragbarer Generator Kohler GM93357-KP2 herunter. Kohler GM93357-KP2 4 Seiten. Oil pan heater kits for 24rcl, 30rcl, and 38rclb

Kohler GM93357-KP2 Einbauanleitung
Original Issue Date: 6/14
Model: 24RCL, 30RCL, and 38RCLB
Market: Residential/Light Commercial
Subject: Oil Pan Heater Kits GM93357-KP1-QS and GM93357-KP2
Introduction
The oil pan heater warms the oil pan when the ambient
temperature falls below 4_C (40_F), making starting
easier and warmup quicker. See Figure 1 for heater kit
specifications.
The adhesive application of the oil pan heater allows for
a quick and easy installation.
illustrations of installed heater kits.
Note: The oil pan heater must be connected to a utility
power source.
Supply a utility power source for the oil pan heater if one
is not already available. See the drawings supplied with
the generator set for conduit/stub--up locations.
2
1
1. Cord
2. Ambient temperature sensor
3. Oil pan heater
Figure 2 Oil Pan Heater (120 VAC and 240 VAC Shown)
INSTALLATION INSTRUCTIONS
See Figure 2 for
3
GM93357-KP1-QS
For the 120 VAC kit, the oil pan heater cord plugs into a
120 VAC receptacle. For the 240 VAC kit, the oil pan
heater cord connects directly to a 240 VAC power
source.
Read the entire installation procedure before beginning
installation. Perform the steps in the order shown.
Kit Number
GM93357-KP1-QS
Voltage
Amps
Watts
Thermostat ON
Thermostat OFF
Figure 1 Heater Specifications
2
1
GM93357-KP2
TT-1633
6/16b
GM93357-KP2
120 VAC
240 VAC
1.3
0.6
150
150
4 ± 4_C (40 ± 7_F)
16 ± 3_C (60 ± 5_F)
3
GM93357