12
24V dc FLEX I/O 16 Sink Input Module
Specifications - 24V dc Input Module Cat. No. 1794 IB16
Storage Temperature IEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold)
IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat)
IEC 60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal
Shock)
-40 to 185 F (-40 to 85 C)
Relative Humidity
IEC 60068-2-30 (Test Db, Unpackaged, Nonoperating Damp
Heat)
5 to 95%, noncondensing
Shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Operating
30g
Nonoperating
50g
Vibration
IEC 60068-2-6 (Test Fc, Operating)
5g @ 10-500Hz
ESD Immunity
IEC 61000-4-2
4kV contact discharges
8kV air discharges
Radiated RF Immunity
IEC 61000-4-3
10V/m with 1kHz sine-wave 80% AM from 30MHz to
1000MHz
IEC 61000-4-4
EFT/B Immunity
+2kV @ 5kHz on signal ports
Surge Transient
IEC 61000-4-5
Immunity
+1kV line-line (DM) and +2kV line-earth (CM) on signal
ports
IEC 61000-4-6
Conducted RF
Immunity
10V rms with 1kHz sine wave 80% AM from 150kHz to
80MHz
Emissions
CISPR 11:
Group 1, Class A (with appropriate enclosure)
Enclosure Type Rating
None (open-style)
2
Conductors Wire Size
12 gauge (4mm
) stranded copper wire maximum rated at 75
or greater
3/64 inch (1.2mm) insulation maximum
1
Category
2
Specifications continued on next page.
Publication 1794 IN072C-EN-P - October 2001