AB Quality ArmorPoint 1738-IB2M12 Installationsanleitung Handbuch - Seite 7

Blättern Sie online oder laden Sie pdf Installationsanleitung Handbuch für E/A-Systeme AB Quality ArmorPoint 1738-IB2M12 herunter. AB Quality ArmorPoint 1738-IB2M12 13 Seiten.

Communicate With
Your Module
1738-IB8M23 and 1738-IV8M23
1
8
9
7
2
10 10
12 12
6
3
11 11
4
5
43681
Make sure all connectors and caps are securely
ATTENTION
tightened to properly seal the connections against
leaks and maintain IP67 requirements.
I/O messages are sent to (consumed) and received from (produced)
the modules. These messages are mapped into the processor's
memory. These modules produce 1 byte of input data (scanner Rx -
status). They do not consume I/O data (scanner Tx).
Default Data Map for the Modules
1738-IB2M12 Module
Message size: 1 Byte
7
6
Produces (Rx)
Where: 0 = off, 1 = on
1738-IB4M8, -IB4M12, and -IV4M12 Modules
Message size: 1 Byte
7
6
Produces (Rx)
Not Used
Where: 0 = off, 1 = on
ArmorPoint 24V dc Input Modules, Series A
(view into connector)
Pin 1 - Input 0
Pin 7 - Input 6
Pin 2 - Input 1
Pin 8 - Input 7
Pin 3 - Input 2
Pin 9 - Return (Com)
Pin 4 - Input 3
Pin 10 - Return (Com)
Pin 5 - Input 4
Pin 11 - 24V dc
Pin 6 - Input 5
Pin 12 - Chassis
5
4
3
2
1
Not Used
Ch1
5
4
3
2
1
Ch3
Ch2
Ch1
Publication 1738-IN002B-EN-E - November 2004
7
0
Ch0
Channel status
0
Ch0
Channel status