AB Quality ArmorPoint 1738-IB4M8 Installationsanleitung Handbuch - Seite 9

Blättern Sie online oder laden Sie pdf Installationsanleitung Handbuch für E/A-Systeme AB Quality ArmorPoint 1738-IB4M8 herunter. AB Quality ArmorPoint 1738-IB4M8 13 Seiten.

Specifications

ArmorPoint Digital Input Modules
Inputs per Module
Voltage, Off-State Input, Maximum
Voltage, On-State Input,
Maximum
Minimum
Nominal
Current, Off-State Input, Maximum
Current, On-State Input,
Maximum
Minimum
Nominal
Input Impedance,
Maximum
Nominal
Input Delay Time OFF to ON
Indication
Probable Cause
Network Status
Off
Device is not on line:
- Device has not completed dup_MAC_ID test.
- Device not powered - check module status indicator.
Flashing Green
Device is on line but has no connections in the established state.
Green
Device is on line and has connections in the established state.
Flashing Red
One or more I/O connections in timed-out state.
Red
Critical link failure - failed communication device. Device
detected error that prevents it from communicating on the
network.
Flashing Red/Green
Communication faulted device - the device has detected a
network access error and is in communication faulted state.
Device has received and accepted an Identity Communication
Faulted Request - long protocol message.
Indication
Probable Cause
I/O Status
Off
Input is in the off state
Yellow
Input on
Following are specifications for the 1738 ArmorPoint digital input
modules.
1738-IB2 - 2 (1 group of 2) nonisolated, sinking
1738-IB4 - 4 (1 group of 4) nonisolated, sinking
1738-IV4 - 4 (1 group of 4) nonisolated, sourcing
1738-IB8 - 8 (1 group of 8) nonisolated, sinking
1738-IV8 - 8 (1 group of 8) nonisolated, sourcing
5V dc
28.8V dc
10V dc
24V dc
1.5 mA
5 mA
2 mA
4 mA @ 24V dc
4.7 kΩ
3.6 kΩ
0.5 ms hardware + (0-63 ms selectable
ArmorPoint 24V dc Input Modules, Series A
1
)
Publication 1738-IN002B-EN-E - November 2004