Changing Mounting Positions
The actuator can be mounted in 90 increments around the valve shaft.
1. Discontinue flow, relieve pipeline pressure and close valve.
Accidental operation of power actuator can cause personal injury or equipment damage.
Disconnect and lock out power to actuator before servicing.
2. Remove the actuator from the valve. See "Removing Actuator" section.
3. Rotate the actuator to the desired position.
4. Install the actuator on the valve. See "Installing Actuator" section.
Troubleshooting
Condition
Actuator closes to wrong
position
Actuator opens to wrong
position
Actuator will not fully operate
valve
Actuator rotates wrong
direction
August 2012
Cylinder Operated G-Series Actuator
Possible Cause
Closed position stop is set
incorrectly
Open position stop is set
incorrectly
Cylinder pressure is low
Piston seal in cylinder is leaking
Pipeline obstruction in valve is
preventing closure
Air connections to cylinder are
incorrect
Page 15
DeZURIK
Corrective Action
Adjust closed position stop. See
Adjusting Position Stops section
Adjust open position stop. See
Adjusting Position Stops section
Increase cylinder pressure. Do
not exceed 100 psi (69 kPa).
Replace piston seal(s). See
Cylinder instructions.
Remove obstruction
Reverse air connections to
cylinder