COZY BFT102 and Handbuch für Installation und Betrieb - Seite 12

Blättern Sie online oder laden Sie pdf Handbuch für Installation und Betrieb für Heizgerät COZY BFT102 and herunter. COZY BFT102 and 18 Seiten. Blue flame vent free heaters
Auch für COZY BFT102 and: Handbuch für Installation und Betrieb (19 seiten), Handbuch für Installation und Betrieb (19 seiten)

The pilot pressure has been pre-set at the factory and with proper supply pressure will provide a safe,
CORRECT
FIGURE 7
All orificing and pressure setting was done at the factory and, with correct supply pressure will provide a
safe, efficient source of heat. If installed above 2,000 ft. elevation, the main burner orifice must be changed.
Orifice change must be completed by a qualified installer or service technician. See orifice chart on Page 10
for correct size. If there is any question about the manifold pressure, have a qualified serviceman check
using a manometer. The manifold pressure should be 3.0" w.c. for natural gas and 10.0" w.c. for L.P. gas.
A proper burner flame will have a soft blue outer mantel approximately 3.5 in. tall with a darker blue inner
mantel approximately 1/4" tall.
INNER
MANTEL
1/4"
CORRECT FLAME

PROPER OPERATION

ODS / PILOT FLAME
reliable ignition source. See Figure 7.
INCORRECT -
LOW PRESSURE
BURNER FLAME
OUTER
MANTEL
3-1/2"
FIGURE 8
Page 12
INCORRECT - OXYGEN
LEVEL DROPPING
INCORRECT FLAME