Elevate Unit
Accum ulation of water and ice in base pan m ay
cause equipm ent dam age.
Elevate unit per local clim ate and code requirem ents to
provide clearance above estim ated snowfall level and
ensure adequate drainage of unit.
areas
where
prolonged
encountered.
If conditions or local codes require the unit be attached
to pad or m ounting fram e, tie down bolts should be used
and fastened through knockouts provided in unit base pan.
Roof Top Installations
Mount on level platform or fram e 6 inches above roof
surface. Place unit above a load-bearing wall and isolate
unit and tubing set from structure. Arrange supporting
m em bers to adequately support unit and m inim ize
transm ission of vibration to building. Ensure roof structure
and anchoring m ethod is adequate for location. Consult
local codes governing rooftop applications.
Roof m ounted units exposed to winds above 5 m ph
m ay require wind baffles to achieve adequate defrost. A
sheet m etal baffle should be spaced 6-1/2" from the fall of
the coil. The height should cover the face of the coil and
the length should be 6" from the access panel.
NOTE: Unit m ust be level to within ± 2 (± 3/8 in./ft) per
com pressor m anufacturer specifications.
Clearance Requirements
W hen installing, allow sufficient space for airflow
clearance, wiring, refrigerant piping, and service.
proper airflow, quiet operation and m axim um efficiency.
Position so water, snow, or ice from roof or eaves cannot
fall directly on unit.
506162-02
Use snow stand in
freezing
tem peratures
DO LOCATE THE UNIT:
!
W ith proper clearances on sides and top of unit
!
On a solid, level foundation or pad
!
To m inim ize refrigerant line lengths
DO NOT LOCATE THE UNIT:
!
On brick, concrete blocks or unstable surfaces
!
Near clothes dryer exhaust vents
!
are
Near sleeping area or near windows
!
Under eaves where water, snow or ice can fall
directly on the unit
!
with clearance less than 2 ft. from a second unit
!
with clearance less than 4 ft. on top of unit
Operating Ambient
The m inim um outdoor operating am bient in cooling
m ode is 55 F, and the m axim um outdoor operating
am bient in cooling m ode is 125 F. The m axim um outdoor
operating am bient in heating m ode is 66 F.

Indoor Coil Piston Selection

The outdoor heat pum p section m ust be m atched to a
factory approved indoor section. It is m andatory that the
installer ensure that the correct piston is installed in the
indoor section. If necessary rem ove the existing piston and
replace it with the correct piston
instructions for details of changing the piston.
your distributor for accessory piston kits.
13 SEER Heat Pum p Indoor Piston Sizes
Unit Size
For
The evaporator coil may use an expansion valve (TXV) in place of piston.
NOTE: If a TXV is installed a hard start kit is required on
all m odels with reciprocating com pressors.
sheet for proper kit selection.
14 SEER Heat Pump M odels
All 14 SEER heat pum p m odels are only rated with TXV on
the indoor side.
14 SEER Heat Pump Indoor TXV
Unit Size
18 thru 36
42 thru 48

Refrigeration Line Sets

Use only refrigerant grade copper tubes.
system s m ay be installed with up to 50 feet of line set (no
m ore than 20 feet vertical) without special consideration
(see long line set guidelines).
Issue 0847
Indoor (Cooling) Piston Size
2HP13
18
.055
24
.063
30
.068
36
.076
42
.076
48
.082
60
.098
See
indoor unit
Contact
4HP13
.051
.055
.059
.070
.070
.082
.082
See spec
TXV Kit
TXV3
TXV5
Split