CP Electronics MWS3 Produktdaten und Installationsblatt - Seite 2
Blättern Sie online oder laden Sie pdf Produktdaten und Installationsblatt für Sicherheitssensoren CP Electronics MWS3 herunter. CP Electronics MWS3 2 Seiten. Multi-sense microwave presence detector
D
P
ETECTION
ATTERNS
IMPORTANT NOTICE!
This device should be installed by a qualified electrician
in accordance with the latest edition of the IEE wiring
regulations.
IDEAL FOR CORRIDOR
OR AISLE APPLICATIONS
IDEAL FOR CORRIDOR
OR AISLE APPLICATIONS
IDEAL FOR OPEN PLAN
AREAS AND OFFICES
Due to our policy of continual
p r o d u c t
Electronics reserves the right to
alter
product without prior notice.
F
F
AULT
INDING
LOAD DOES NOT COME ON
Check to see if the live supply to the circuit is good. Strap across the L
and LIVE OUT terminal to turn the load on.
If the supply and wiring are good, check the LUX level setting. In-
crease the LUX level setting to allow the controller to turn on at higher
ambient natural light level.
LIGHTS DO NOT GO OFF
Ensure that the area is left unoccupied for a greater time period than
the time out period set using the switch.
Make sure that the sensor is not adjacent to vibrating surfaces or
objects (e.g. ventilation equipment).
The unit may pick up movement through thin partitions or walls. Re-
duce the sensitivity by turning the adjuster anticlockwise.
The unit may pick up movement that occurs behind the sensor. Re-
duce the sensitivity by turning the adjuster anticlockwise.
S
PECIFICATION
LOAD
10 Amp resistive load
8 Amp incandescent lighting
5 Amp fluorescent lighting
3 Amp compact fluorescent lighting
3 Amp low energy lighting
3 Amp low voltage lighting (switch primary of transformer)
Fluorescent lighting (max 6 fittings recommended)
For fluorescent lighting total power factor correction capacitance must
not exceed 40 F.
3 Amp fans and ventilation equipment
Switch SON lighting loads via a contactor
SUPPLY VOLTAGE
TIME OUT PERIOD
LIGHT LEVEL
FIXING METHOD
TERMINAL CAPACITY 1.5 mm
MATERIAL
TYPE
TEMPERATURE
SAFETY
CONFORMITY
P
N
ART
UMBERS
MWS3
Multi-sense microwave presence detector
C.P. Electronics Ltd
Unit 2 Abbey Manufacturing Estate
Mount Pleasant, Wembley
Middlesex. HA0 1RR
Tel:
i m p r o v e m e n t
C P
Fax:
the
specification
of
this
www.cpelectronics.co.uk
220-240 Volts AC 50 Hz
Adjustable 15 seconds to 30 minutes.
Light to dark.
Flush fixing in 86mm hole using clip provided
Surface fixing using integral back plate
2
Flame retardant ABS, fixing clip polypropylene
Class 2
-10° C to 35° C
The microwave radiation emitted by these units
is exteremely low power.
At a distance of > 50mm the power density is
<6% of the ANSI IEEE C95.1 –1991 recom-
mended microwave power density.
At a distance of 5mm from the unit it is <84%
of recommended power density.
EMC-89/336/EEC
LVD-73/23/EEC
+ 44 (0) 20 8900 0671
+ 44 (0) 20 8900 0674
Ref %WD136 Issue 1