CP Electronics ALC-PRM-VFC Produkthandbuch - Seite 4
Blättern Sie online oder laden Sie pdf Produkthandbuch für Zubehör CP Electronics ALC-PRM-VFC herunter. CP Electronics ALC-PRM-VFC 8 Seiten. Ceiling mounted photocell
Basic programming
Parameter
Default
0
Name
Value
SHIFT 1
On
On
Off
Off
Lux on
9
2, 5 & 7
level
(Switch
level on)
Lux off
9
2, 5 & 7
level
(Switch
level off)
Defaults
Shift
4
The functionality of the ALC-PRM-VFC is controlled by a number of parameters which can
be changed or programmed by any of the following devices:
UHS5 Infrared Handset. See below for programmable functions.
UNLCDHS Infrared Handset (with LCD). See user guide for full programming details.
For most basic programming operations the UHS5 handset can be used and the following procedures
are based on using this device.
Point the handset at the Sensor and send the required programming commands to the unit as shown
below.
Valid commands will be indicated by a red LED flash. See page 1 for details of other LED responses.
Note: other functions on the UHS5 which are not shown below are not applicable to this product.
Number of Shift key presses
1
2
3
SHIFT 2
SHIFT 1
SHIFT 2
SHIFT 1
SHIFT 2
SHIFT 1
Button Activation
4, 6 & 9
4, 6 & 9
D
UHS5 Handset Graphics
SHIFT 2
Description
Turn lights on.
Turn lights off.
Lux level setting to prevent the luminaires being
switched on if the ambient light level is sufficient
(adjustable between 1 and 9). The luminaires will
always be switched on at level 9.
Lux level setting to switch the luminaires off the
ambient light level goes above the setting
(adjustable between 1 and 9). Level 9 will always
keep the lights on. This setting can be used for
"window row switching".
Note: the Lux Off Level value must always be
greater than the Lux On Level value.
Returns the unit to the default settings.
Use this button to select the settings in red and
blue signified by the „Shift 1‟ and „Shift 2‟ LEDs