IR cmd
Sw lev on
Switch level on
Lux level setting to prevent the luminaires being switched on if the ambient light
level is sufficient (adjustable between 101 and 199).
Use to provide finer adjustment than parameters opposite.
Sw lev off
Switch level off
Lux level setting to switch the luminaires off during occupancy if the ambient light
level goes above the setting (adjustable between 101 and 199).
Use to provide finer adjustment than parameters opposite.
DALI on
Provides a permanent voltage to DALI ballasts when DALI has not been imple-
mented correctly in the ballast. Maximum number of ballasts is 10 unless the relay
is disabled then it is 20.
IR cmd
Lux up
Increase light level. Reverts when occupancy cycle complete.
Lux down
Decrease light level. Reverts when occupancy cycle complete.
Scene up
Steps up between 6 pre-defined scenes.
Scene down
Steps down between 6 pre-defined scenes.
Scene #
Select the individual scene, between 0 and 6. (1 = min. output; 2 = 10%; 3 = 25%; 4 = 50%; 5 = 75%; 6 =
100%)
Override on
Permanently overrides the luminaire output on.
Override off
Permanently overrides the luminaire output off.
Cancel
Cancels the on or off override, returning the detector to normal operation.
Set
If sent before using lux up or lux down, it will set the light level as in „ Light lev‟ found „Ch2 (dim) set‟
menu
7. Ch2 (dim) set Menu (con)
Description
Description
Special Menu
Default
Products
None
-DD & MWS7
only
None
-DD & MWS7
only
Off
-DD & MWS7
only

8. User Menu

Products
All
All
-DD & MWS7
only
-DD & MWS7
only
-DD & MWS7
only
All
All
All
All
7