Advanced programming (UNLCDHS)
Default settings for buttons
Buttons
Events
1 and 2
Single press
Press and hold
Release from hold
3 and 4
Single press
Press and hold
Release from hold
Parameter Name
Default Value
Individual Input Channel - continued
Event number
See table
above
Button events
0
Input function
0
Local On Scene /
1
Level
Local Step Scene /
1
Level
8
Control function
Scene recall
Raise light level
Circuit stop
Scene recall
Lower light level
Circuit stop
Range / options
0 to 4
Events for a momentary switch
0 – No event
1 – Single press
2 – Press and hold
3 – Release from hold
3 – Centre button and other button
single press
0.
None
1.
On scene recall
2.
Off scene recall
3.
Scene raise
4.
Scene lower
5.
Scene stop
6.
On at last scene
7.
On at last manual scene
8.
On at last level
9.
On circuit absolute
10. Off circuit absolute
11. Circuit raise
12. Circuit lower
13. Circuit stop
14. User override on
15. User override off
16. User override release
17. System override on
18. System override off
19. System override release
20. Emergency test start
21. Emergency test stop
Scene Mode
1 to 220
1 to 20 will select local ON scene.
101 to 220 will select Area ON scene
Circuit Mode
0 to 100 will select Local ON Level
101 to 201 will select Area ON Level.
Scene Mode
1 to 220
1 to 20 will select local Step scene.
101 to 220 will select Area Step
scene
Circuit Mode
0 to 100 will select Local Step Level
101 to 201 will select Area Step
Level.
Description
Set event number for the button
Selects the Input Parameters which are to be modified on the next IR
command.
Input switch can be configured to be active on one of the event
selected.
Selects one of the input functions for the event.
User override will override presence detection and lights will remain
On/Off until new command is issued from Scene Plate.
System Override will override presence detection and any other
command issued by Scene Plate. It is like permanent override only
disabled by system override release command.
Starts/Stop Emergency test.
The local scene request sent to all devices with the same Local Code,
when movement is detected. If input function selected is Scene recall
then this parameter can act as local or area scene depending on the
value set.
If input function selected is On circuit absolute or Off circuit absolute
then if value is set between 0 to 100 it will set Local ON level to the
level set.
If value is set between 101 to 201 it will set Area ON Level to
normalized to 0 to 100% level.
Value of 101 to 201 will correspond to 0 to 100% of light level.
If a Local Step Scene is specified this will be requested first when the
Sensor switches off. If a Step Scene is not specified, or if it times out,
the Local Of f Scene will be implemented.
Step Scene is only implemented when no movement is detected
during timeout period.