1- LAYOUT AND SETTINGS
1.1 Optical board (QBASE)
MA
R:
OUT
Black wire " –
Red
wire"+
OUT
1.1.1 Terminal block MA.
"+" >>> NEGATIVE AT REST
"–" >>> POSITIVE AT REST
"S" >>> SYNCHRONISM
Connect to the terminal block MA (clamps "+" & "–") the end line resistor as shown in figure (FIG.1) . For the
R:
value keep to the instruction of the certified central unit.
1.1.2 Connector CMA.
Connect the connector of the visual device from the cover of the panel.
1.2 Acoustic board (AVD FJ/CPD)
1.2.1 JUMPERS FUNCTION
To select the type of function desired keep to the instruction below.
INSTALLATION MANUAL
–
Fire alarm visual & sounding device for fire signalling conform to regulation
" connected to "– in" of the board AVD FJ/CPD (
OUT
" connected to "+ in" of the board AVD FJ/CPD (
Black wire "– in" connected to " –
wire "+ in" connected to "+
Red
+in
– in
SW4
Type of suond
selector
SW4
Swap of frequency Sound
EN54-3 & EN54-23.
factory connection
)
factory connection
" of the board QBASE (
OUT
" of the board QBASE (
OUT
CM4
CM5
SW4
CM4
Connection board QBASE
(factory connection)
OPEN
(factory set
)
White wire connected to CM4
of board AVD FJ/CPD
(
)
factory connection
)
factory connection
CM3
CM3
Output piezo
CLOSED
up)
Fixed Sound
®
FIG 1
)
factory connection