CPS AR2700A Betriebshandbuch - Seite 12
Blättern Sie online oder laden Sie pdf Betriebshandbuch für Prüfgeräte CPS AR2700A herunter. CPS AR2700A 17 Seiten. Refrigerant recovery / recycling system
TROUBLE SHOOTING / OPERATION
High Pressure Indication - During recovery or tank refill if a high pressure condition
trips the HP limit switch, the compressor relay is deactivated, an alarm sounds and the
screen shown below is displayed.
HP
OL
Tank Overfill Indication - During recovery if the weight of the refrigerant in the tank
exceeds the maximum refill refrigerant weight the compressor relay is deactivated and
power is disconnected from the compressor. The message below is displayed and the
alarm is sounded.
rC
OL
At anytime, and regardless of the units chosen or the level of tare, if more than 100 kg
or 220.5 lb is placed on the weighing platform, an overload message is displayed as
shown below.
lbs
OL
oz
Unit's Compressor Fails to Start - If the compressor is unequalized, it may not start.
To equalize, open oil drain valve for 10 seconds then close. Try restarting compressor.
kg
Solution: Check that both tank valves and both tank hose
valves are open.
Solution: Run the air purge routine. Presence of air in
recovery tank can cause high pressure to exist.
g
kg
Solution: Make sure tank settings were properly inputted.
Solution: Run Charge mode, Charge 10 lbs. of refrigerant
into an evacuated cylinder. Save for future use.
g
Solution: Make sure the tank used when full will not
exceed 220 lbs maximum.
Solution: Check scale calibration
Compressor Fails To Start
12