Type (1/4 turn electric actuator)
Housing type
IP protection (EN60529)
Corrosion resistance (outdoor and
indoor use)
Temperature
Hygrometry
Pollution degree
Altitude
Extended environmental conditions
Sound level
Weight
Nominal torque
1/4 turn travel time (standard ER)
1/4 turn travel time (slow ER)
1/4 turn travel time (ER POSI)
Mounting actuator base (ISO5211)
Swing angle
Mechanical end stops
Manual override
Direction of rotation
Voltage ±10%
Voltage ±10%
(BBPR GS2)
Frequency
Power consumption
Overvoltage category
Torque limiter
Duty cycle (CEI34)
Limit switches maximal voltage
Limit switches maximal current
Electrical wiring
Inrush current
CR-TEC
14

TECHNICAL DATA

ER10
Small housing (see p.19)
Housing: PA6 UL94V0 + 25% GF and cover: PA6 UL94V0
Raw material : 304L Stainless Steel or Steel + Zn treatment
maximum relative humidity 80 % for temperatures up to 31 °C decreasing linearly
MECHANICAL DATA
10Nm
20Nm
11s
Star 14
F03-F04-F05
ELECTRICAL DATA
15W (0.08A) cos j = 0.75
TRANSIENT OVERVOLTAGES up to the levels of OVERVOLTAGE CATEGORY ll
TEMPORARY OVERVOLTAGES occurring on the MAINS supply
1 ISO M20 cable gland and 1 DIN43650 3P+T connector
Circuit breaker type D, nominal current according the number of actuators (max. 4 ac-
tuators) or use a inrush current limiter at the output of the circuit breaker.
Engineering Inc.
ER20
ER35
IP66
(dusts, water spraying « flow <12.5 L/min »)
-10°C to +55°C (BBPR GS2: -10°C to +40°C)
to 50 % relative humidity at 40 °C
altitude up to 2 000 m
Outdoor use and in WET LOCATION
61 dB
1 Kg
35Nm
11s
25s
25s
90° (others on request)
90° +/- 5°
Out axle
Anticlockwise to open
100 V to 240 V AC 50/60 Hz and 100 V to 350 V DC
15 V to 30 V AC 50/60 Hz and 12 V to 48 V DC
100 V to 240 V AC 50/60 Hz and 100 V to 350 V DC
24 V to 30 V AC 50/60 Hz and 24 V to 48 V DC
50/60Hz
Electric
50%
4 to 250V AC/DC
(Overvoltage category II)
1mA to 5A max
[email protected] • www.crtec.com • 203-318-9500
ER35
ER60
large housing (see p.19)
2.1 Kg
35Nm
60Nm
7s
12s
41s
79s
41s
79s
Star 22
F05-F07
45W (0.15A) cos j = 0.75
ER100
100Nm
23s
119s
119s