2 Enter changes. Configurable environment settings are:
Parameter
Sensor name
Temperature
High threshold (temperature)
Low threshold (temperature)
Hysteresis (temperature)
High threshold (humidity)
Low threshold (humidity)
Hysteresis (humidity)
Input #1 and Input #2
when closed and when open
Description
The name given to the EMP. Dell recommends using a name that
identifies the location of the EMP.
Choice of the temperature unit (°C or °F) from the list.
If the temperature exceeds the set threshold, a notification is triggered if
enabled. The default value is 40°C / 104°F.
If the temperature falls below the set threshold, a notification is triggered
if enabled. The default value is 5°C / 41°F.
Hysteresis must be set to prevent multiple notifications if temperature
fluctuates around a threshold. The default value is 2°C / -3.6°F.
The high alarm disappears when the value drops below the high threshold
minus hysteresis value.
The low alarm disappears when the value returns above the low threshold
plus the hysteresis value.
If the humidity exceeds the set threshold, a notification is triggered if
enabled. The default value is 90%.
If the humidity falls below the set threshold, a notification is triggered if
enabled. The default value is 5%.
Hysteresis must be set to prevent multiple notifications if humidity
fluctuates around a threshold. The default value is 5%.
The high alarm disappears when the value drops below the high threshold
minus the hysteresis value.
The low alarm disappears when the value returns above the low threshold
plus the hysteresis value.
An identifier corresponding to the acquired contact (for example: rack
door, air conditioning, or generator unit). The maximum length is 28
characters.
The names associated with the two contact positions (for example "open"
and "closed" for a door, "on" and "off" for a generator).
Configuring the EMP