Dell PowerEdge R630 Handbuch zur Installation - Seite 15

Blättern Sie online oder laden Sie pdf Handbuch zur Installation für Server Dell PowerEdge R630 herunter. Dell PowerEdge R630 18 Seiten.
Auch für Dell PowerEdge R630: Erste Schritte (2 seiten), Erste Schritte (2 seiten)

Dell PowerEdge R630 Handbuch zur Installation
Dell R630 server power specifications
Specification
BTU
Voltage
Plug Type
Circuit Breaker
Pole
AMP Draw
Note:
The above power configuration is based on the following example:
• Two E5-2620 Processors
• Two 495W power supplies
• Two 300GB HDDs
• CPU load 100%
• Eight 4 GB 1866 MT/s DIMMs
Installing the server in the rack
About this task
Note:
Although not used frequently, Avaya customers are required to have a monitor, USB keyboard,
and USB mouse available for use by installation and/or servicing technicians.
Before you begin
Get the Rack Installation Instructions that are shipped with the hardware for more information. If not
shipped with the hardware, see the Dell documentation Web site for instructions.
Procedure
1. Examine contents of shipping container (Avaya provided equipment), and ensure that the 6-
digit material code on the order matches the 6-digit material code on the shipping container.
2. Verify that the rack is installed according to the manufacturer's instructions and in
accordance with all local codes and laws. Verify that the rack is grounded in accordance with
local electrical code.
3. Remove the cabinet doors, if necessary.
4. Attach the rails to the rack
November 2015
Value
1058 BTU/hr
110 VAC (100–240 VAC auto-ranging 50/60 Hz)
NEMA 5-15P
15 amp
1
2.8 A, 310 W (based on 110 voltage)
Installing the Dell PowerEdge R630 Server
Comments on this document? [email protected]
Dell R630 server power specifications
15