Attic Insulation Shield: The Attic Insulation Shield must
be installed where the chimney passes into an attic. Its
purpose is to maintain clearances from loose packed or
blown insulation from the chimney. If an Attic Shield is not
used the chimney needs to be enclosed within a framed
enclosure. Always maintain a 2" air-space clearance to
combustibles. Install the shield as follows:
Remove any insulation or debris from attic floor around
•
the framed opening.
•
Assemble chimney sections above the Firestop to
a height that extends beyond the height of the attic
insulation shield.
•
Slip the Attic Insulation Shield over the chimney until
the base sits squarely on the framed opening.
•
Secure the Attic Insulation Shield to the top of the
framed opening using nails or screws. See FIG. 8.
NAILS OR
SCREWS
FLOOR/
CEILING
Termination: NFPA 211, "Standard for Chimneys,
Fireplaces, Vents, and Solid Fuel-Burning Appliances",
states that chimneys shall extend at least three feet above
the highest point where it passes through the roof of a
building, and at least two feet higher than any portion of a
building within ten feet. See FIG. 9.
3 FEET
MINIMUM
ABOVE
ROOFLINE
CHIMNEY
ATTIC
INSULATION
SHIELD
FIRESTOP
FIG. 8
2 FEET ABOVE ANY POINT WITHIN
10 FEET HORIZONTALLY
FIG. 9
For chase enclosures, install the chase top cover (supplied
by others) to the chase enclosure. Cut a hole in the chase
top cover the same diameter as the base of the cone on
the flashing. Attach the Flashing to the top of the chase
cover, sealing with a non-hardening waterproof sealant.
Secure in place with screws or rivets. See FIG. 10.
SCREW OR
RIVET STRAPS
TO FLASHING
RADIATION SHIELD
CHASE COVER
(SUPPLIED
BY OTHERS)
Attach the storm collar around the chimney above the
screen of the flashing. Secure in place with the locking
tab and button. Seal around the storm collar with a non-
hardening waterproof sealant. Attach the Termination
Cap to the chimney by sliding the male to female joint
connection together and secure in place with (4) sheet
metal screws provided. See FIG. 11.
SELF-TAPPING
SCREWS
APPLY SEALANT
5
FLASHING
SCREW OR RIVET
TO CHASE COVER
APPLY SEALANT
CHIMNEY
CHASE
FIG. 10
TERMINATION
STORM COLLAR
FLASHING
FIG. 11
NAIL TO CHASE