Auch für Dell PowerVault TL2000: Anmerkungen zur Veröffentlichung (3 seiten), Erste Schritte (38 seiten), Faq (26 seiten), Schnellstart-Handbuch (7 seiten), Software-Handbuch (16 seiten), Konfigurationshandbuch (22 seiten), Wichtige Informationen Handbuch (10 seiten), Benutzerhandbuch Addendum (2 seiten), Handbuch "Erste Schritte (3 seiten), Anbringung von Anweisungen (17 seiten), Broschüre (4 seiten)

Dell PowerVault TL2000 Benutzerhandbuch
CAUTION:
Removing components from the upper positions in the
rack cabinet improves rack stability during relocation.
Follow the general guidelines as listed below whenever
you relocate a populated rack cabinet within a room or
building:
v Reduce the weight of the rack cabinet by removing
equipment starting at the top of the rack cabinet. When
possible, restore the rack cabinet to the configuration of
the rack cabinet as you received it. If this configuration
is not known, you must do the following:
– Remove all devices in the 32U position and above.
– Ensure that the heaviest devices are installed in the
bottom of the rack cabinet.
– Ensure that there are no empty U-levels between
devices installed in the rack cabinet below the 32U
level.
v If the rack cabinet you are relocating is part of a suite of
rack cabinets, detach the rack cabinet from the suite.
v Inspect the route that you plan to take to eliminate
potential hazards.
v Verify the route that you choose can hold the weight of
the loaded rack cabinet. Refer to the documentation that
comes with your rack cabinet for the weight of a loaded
rack cabinet.
v Verify that all door openings are at least 762 x 2032 mm
(30 x 80 inches).
v Ensure that all devices, shelves, drawers, doors, and
cables are secure.
v Ensure that the four leveling pads are raised to their
highest position.
v Ensure that there is no stabilizer bracket installed on the
rack cabinet during movement.
v Do not use a ramp inclined at more than ten degrees.
v Once the rack cabinet is in the new location, do the
following:
– Lower the four leveling pads.
– Install stabilizer brackets on the rack cabinet.
– If you remove any of the devices from the rack
cabinet, repopulate the rack cabinet from the lowest
position to the highest position.
v If a long distance relocation is required, restore the rack
cabinet to the configuration of the rack cabinet as you
received it. Pack the rack cabinet in the original
packaging material, or equivalent. Also lower the
leveling pads to raise the casters off of the pallet and
bolt the rack cabinet to the pallet.
Safety and Environmental Notices
xvii