Dell Force10 S55 Handbuch - Seite 19

Blättern Sie online oder laden Sie pdf Handbuch für Schalter Dell Force10 S55 herunter. Dell Force10 S55 50 Seiten.
Auch für Dell Force10 S55: Schnellstart-Handbuch (29 seiten)

Dell Force10 S55 Handbuch
Step
Task (continued)
Attach the bracket "ears" to the rack or cabinet posts, using two screws for each bracket. Ensure the screws are
2
tightened firmly.
PSU0

Attach ground cable

The S55 is shipped with 1 10-32 screws for attaching a ground cable to the chassis. The cable itself is not
included. Dell Force10 recommends a 6AWG one-hole lug, #10 hole size, 63" spacing (not included in
shipping) to properly ground the chassis. The one-hole lug must be a UL recognized, crimp-type lug.
NOTE: The rack installation ears are not suitable for grounding.
CAUTION: Grounding conductors must be made of copper. Do not use aluminum conductors.
Follow these steps to connect the ground cable to the chassis.
NOTE: Coat the one-hole lug with an anti-oxidant compound prior to crimping.
Bring any un-plated mating surfaces to a shiny finish, and coat with an anti-oxidant prior to mating.
Plated mating surfaces must be clean and free from contamination.
Step
Task
Take the (1) 10-32 screw from the package.
1
Cut cable to desired length. Cable length must facilitate the proper operation of fault interrupt circuits. Dell
2
Force10 recommends using of the shortest cable route allowable.
PSU1
Rack Mounting
ears
Rack/Cabinet
Post
Install the S55
|
19