AW-Lake M9480220 Installations-, Betriebs- und Wartungshandbuch - Seite 8
Blättern Sie online oder laden Sie pdf Installations-, Betriebs- und Wartungshandbuch für Zubehör AW-Lake M9480220 herunter. AW-Lake M9480220 18 Seiten. The edge flow sensor with bluetooth
o Off: No filtering
o Low: Most filtered, low sensitivity (Corner frequency ¼ Hz)
o Medium: Medium sensitivity (Corner frequency 1 HZ)
o High: least filtered, High sensitivity (Corner frequency 10 Hz)
Flow Units:
Real time flow rate units
Flow Time Base:
Real time flow time base unit
Max Flow Rate:
The flow rate at which the analog output should be at its max
Max Flow Units:
Selects what unit to scale flow in
*Flow units will affect Max Flow Rate. Verify both after changing flow units.
Max Flow Time Base:
*Time base will affect the Max Flow Rate. Verify max flow rate is correct after changing time
base.
Bluetooth Name:
The name that will appear when searching for the device. Connection will
be lost after changing the Bluetooth name and will require reconnection. Name is limited to 19
characters. Some characters on the phone are invalid to use. Examples: $, %, ^ symbols.
Output Settings
This menu will provide the option to force one or both outputs to a
certain value. Along with this ability, Voltage output type will also be
selectable. (Figure 5)
To activate, move the slider to the right. Enter in desired forced
output and press SET to store information.
*Note: information will not be stored until SET is pressed and forced value
will revert back to previous value or state if output value is outside of the
range.
Forced output limitations: When forcing an output, it must be in
between the analog out specifications and will go to the third decimal
place.
Ex. 4-20mA output Forced output: 6.25mA
0-10V output
Forced output: 7.5V
Can be set to Sec, Min, Hours, and Days.
Figure 5: Output Settings
8 |
P a g e