Allmatic ARGO 2 Series Handbuch - Seite 4

Blättern Sie online oder laden Sie pdf Handbuch für Kontrolleinheit Allmatic ARGO 2 Series herunter. Allmatic ARGO 2 Series 9 Seiten. Switchboards, programmable for 1 or 2 motors with independent slowdown control

6.2 Torque adjusting of the motor.
The control unit Is furnished with a trimmer for adjusting the torque supplied to the motor, in order to limit the force of gate against some obstacles
that might get in the way during motion (for ex. poor/fair functioning of photocells).
POWER
For regulating the torque applied by the motor, proceed as follows:
-
+
270°
6.3 Automatic re-closing function.
The automatiic re-closing function is an operation that enables the automatic re-closing of gate when the pause time selec-
A. RECL. TIME
ted by the "A. RECL. TIME" is over.
-
+
The enabling or disabling of function is given from the same trimmer, that is:
270°
NOTA: The successive learning can now be executed also with the memorized tranmitter. The operative modalities are
reported here following.
7. Funzioni selezionabili tramite DIP-SWITCH.
7.1 Step-by-step function.
1 2
3
4 5 6 7
8
9 10
1 2
3
4 5 6 7
8
9 10
It is possible to change the way the control unit responds to commands given by the remote control or step-by-step key (pulse button):
Step-by-step order may be given by a special input (see pulse switch on terminal block), or by pushing the first key of a memorised transmitter (see
section 5 learning transmitter).
7.2 Water hammer.
If the automation mechanism provides for an electric lock and this is enabled, when the gate is closed, it is advisable for the motor to operate in clo-
sing state for a shortly period before starting the opening one. This function makes it possible to open the electric lock in any case, even in bad wea-
ther conditions (such as in the event of ice).
1 2
3
4 5 6 7
8
9 10
1 2
3
4 5 6 7
8
9 10
7.3 Safety and protection photocells.
When an obstacle interfers with the beam emitted by the transmitter and receiver photocells, the sames modify control unit condition as follows:
1 2
3
4 5 6 7
8
9 10
1 2
3
4 5 6 7
8
9 10
6-1622192
rev. 14
21/09/2012
Act on trimmer regulation to set the torque desired, keeping in mind that the trimmer is at the minimum level when loca-
ted in the extreme counter-clockwise direction and at the maximum level when located in the extreme clockwise
direction.
Start up the motor and check the torque.
If the regulation is not adecuate, stop the movement and fit the trimmer again, than start up the motor again.
Is advisable to check the torque before regulating the gate movement.
Defining the whole trimmer for extreme counter-clockwise (minimum), the automatic re-closing is disabled.
Defining the whole trimmer for clockwise, on introduct the automatic re-closing.
It is important to change the configuration of the dip-
switch only with power down.
ON
The unit automatically carries out an open-stop-close-stop sequence.
OFF
ON
The unit automatically carries out an open-close-open-close sequence.
OFF
Water hammer is active for opening stage and the electrical lock is controlled through the control unit. The
ON
default cycle provides for a minimum water hammer during the opening phase and for no water hammer
OFF
during the closing one, which may be modified as described in paragraph 8.1.
ON
Water hammer is disable but the electrical lock is still active ( this is very usefull when a magnetic lock
OFF
is present).
A) during the gate opening cycle : if photocells detects an obstacle, the central unit stops the gate. When
ON
the obstacle is removed, the door OPEN cycle resumes until the door is open fully.
OFF
B) during the gate closing cycle: if photocells detects an obstacle, the central unit stops the gate. When
the obstacle is removed, the door OPEN cycle resumes until the door is open fully.
ON
A) during the gate opening cycle: if photocells detects an obstacle, the gate motion continues
OFF
B) during the gate closing cycle: if photocells detects an obstacle, the central unit blocks and invertes
the direction of gate until it is totally opened.
ITA
ENG
FRA
ESP
DEU
POR
4/9