WARNING:
To avoid the risk of fire, explosion, or
electric shock, this product should be
installed, inspected, and maintained by
a qualified electrician in accordance
with all applicable electrical rules and
regulations.
Safety Instruction:
To avoid electric shock:
Be certain electrical power is OFF
before and during installation and
maintenance.
Make sure the supply voltage is the
same as the rated luminaire voltage.
The technical data indicated on the
LED luminaires are to be observed.
Changes
of
the
modifications to the LED luminaire are
not permitted.
Observe
the
national/regional
electrical safety rules and regulations
during installation.
The LEDs of this luminaire are not
replaceable; when the LEDs reach their
end of life, the whole luminaire shall be
replaced.
Power Supply
Part Number
Description
F1PS2B
100-277V, F1, 12k
F1PS2C
100-277V, F1, 18k
F1PS2E
100-277V, F1, 24k
F1PS2F
100-277V, F1, 30k
F1PS5B
347-480V, F1, 12k
F1PS5C
347-480V, F1, 18k
F1PS5E
347-480V, F1, 24k
F1PS5F
347-480V, F1, 30k
F2PS2F
100-277V, F2, 30k
F2PS2H
100-277V, F2, 36k
F2PS2L
100-277V, F2, 48K
F2PS2N
100-277V, F2, 60k
F2PS5F
347-480V, F2, 30k
F2PS5H
347-480V, F2, 36k
F2PS5L
347-480V, F2, 48k
F2PS5N
347-480V, F2, 60k
WARNING: Any replacement power supply
must be a DIRECT REPLACEMENT for the
existing power supply. No changes in lumen
output or AC voltage input permitted.
9100FLM00905 REV A
Page 3 of 18
ProSite Floodlight Replacement Parts & Accessories
1. When opening the driver lid on the
luminaire, loosen the 10-32 captive screws.
F1 models contain 10x screws and F2
models contain 16x screws.
Driver Lid with
Captive Screws
NOTE: The lid is retained to the luminaire via 2x
design
and
locked braided wires.
NOTE: The gasket for the lid should remain in
place upon removal of the lid via an
adhesive backing on the gasket.
2. Open the driver 90° to disconnect the
power supply/supplies from the luminaire.
WARNING: The driver lid cannot be fully
opened while all electrical connections of
the power supplies remain plugged into
luminaire.
3. Unplug all connections to the power supply
that are present:
Type
AC 100-277V
AC 347-480V
DC
DALI
Dimming/
Wireless
4. Once all electrical connections have been
unplugged between the power supply
and the luminaire, the driver lid can then
be fully opened and rested on the
luminaire.
Locked
Braided Wires
Plug
Color
2 Position
White & Black
2 Position
Red & Black
2 Position
Red & Black
2 Position
2x Orange
24 Position
Various
Dialight, 1501 Route 34 South, Farmingdale, NJ, USA 07727
Tel: +1 732 919 3119 Fax: +1 732 751 5778
5. Remove 4x M4 screws that hold the power
supply to the luminaire.
Power Supply M4 Screws
6. Collect the replacement power supply
and install onto lid with 4x M4 screws. Extra
screws provided.
7. Torque to 20-24 in-lbs. [2.3-2.7 N-m].
8. The lid should now be rotated back to the
90° position shown in Step 2 to plug in all
electrical connections.
9. Re-plug all connections to the power
supply:
Type
Plug
AC 100-277V
2 Position
AC 347-480V
2 Position
DC
2 Position
DALI
2 Position
Dimming/
24 Position
Wireless
10. Close the driver lid onto the luminaire
using the 10-32 captive screws.
Torque to 30-33 in-lbs. [3.4-3.7 N-m].
WARNING: When closing the lid, make sure
wires do not get pinched.
11. Power the luminaire on and insure proper
function.
www.dialight.com
Color
White & Black
Red & Black
Red & Black
2x Orange
Various