Miller Blue Star 145 Anwendungshandbuch - Seite 15

Blättern Sie online oder laden Sie pdf Anwendungshandbuch für Inverter Miller Blue Star 145 herunter. Miller Blue Star 145 16 Seiten. Generator power

Miller Blue Star 145 Anwendungshandbuch
Y If unit does not have GFCI receptacles, use GFCI-protected extension cord.
Current In
Load In
Amperes
Watts
5
1200
7
1680
10
2400
15
3600
20
4800
25
6000
30
7000
35
8400
40
9600
45
10,800
50
12,000
*Conductor size is based on maximum 2% voltage drop
Cord Lengths For 240 Volt Loads
Maximum Allowable Cord Length In Feet (Meters)
For Conductor Size (AWG)*
4
6
800
(244)
800
550
(244)
(168)
600
350
(183)
(107)
450
275 (84)
(137)
350
225 (69)
(107)
300 (91)
175 (53)
250 (76)
150 (46)
225 (69)
125 (38)
200 (61)
125 (38)
175 (53)
100 (31)
8
10
700
450
(213)
(137)
500
300 (91)
(152)
350
225 (69)
(107)
225 (69)
150 (46)
175 (53)
100 (31)
125 (38)
75 (23)
100 (31)
75 (23)
100 (31)
75 (23)
12
14
225 (84)
200 (61)
200 (61)
125 (38)
125 (38)
100 (31)
75 (23)
60 (18)
60 (18)
Page 11