FIRE/EXPLOSION HAZARD. This thermostat is not
intended for use in hazardous atmospheres where
flammable vapors, gases, liquids or other com-
bustible atmospheres are present as defined in
the National Electrical Code. Failure to comply can
result in personal injury or property damage.
NOTICE: Type GNIT Thermostats are designed for temperature
control service only. Because they are not fail safe, they should
not be used for temperature limiting duty.
The system designer is responsible for the safety
of this equipment and should install adequate
back-up controls and safety devices with their
electric heating equipment. Where the conse-
quences of failure could result in personal injury or
property damage, back-up controls are essential.
The GNIT Non-Indicating Corrosive Resistant Thermostat is
designed for applications in atmospheres where corrosive material is
present. The double pole/single throw thermostat is available with
either a 5 foot or 12 foot copper capillary which is sleeved with
Note: Do not mount thermostat where it will be subject to vibra-
tion or shock. Do not mount adjacent to a large magnetic contac-
tor, as vibration and shock will cause thermostat to interact errati-
cally — resulting in chattering of the contactor.
The air temperature in and around the thermostat enclosure
should be kept as near to normal room temperature as possible...
© 2010 Chromalox, Inc.
Chromalox

Installation Instructions

Resistant Industrial Thermostat
Features:
• Rugged Design
• Moisture and Corrosion Resistant
• Teflon
®
Covered Capillary/Bulb
• Large Setpoint Dial
• Easy Installation
• Line Voltage
• DPST 25 Amp Switch
Teflon
®
is a registered trademark of DuPont Co.
®
GNIT Moisture and Corrosion
Specifications —
Model
GNIT-5
GNIT-12
Other temperature ranges available. Contact your local Chromalox Sales office.
GENERAL
Teflon
®
designed for 25 amperes resistive loads for either 120 or 240 Vac.
Specifications:
Range
Switch Action
Current
Accuracy
Load Lamp
Capillary Length
Diameter of Teflon
Application Notes
1. Customer external fuse required.
Process Temperature Differential — is variation in controlled
process temperature between maximum, when thermostat turns
OFF and minimum, when thermostat turns ON. This spread in
temperature may be minimized by:
1. Making sure control is mounted to vertical surface. (See Step 1,
MOUNTING.)
2. Avoid excess heating capacity (oversized heaters).
3. Locating control sensing bulb in optimum position between
heat source and work.
MOUNTING
never above 150˚F or below 30˚F.
1. Thermostat must be mounted in a vertical position only.
2. Use sheet metal or wood screws through the four 1/4" diame-
ter mounting holes in baseplate to mount control.
SERVICE REFERENCE
4
DIVISION
SALES
(Supersedes PK479-2)
REFERENCE
AUGUST, 2006
DATE
Temperature
PCN
Volts
Range (˚F)
360946
30 to 220
120/240
360954
30 to 220
120/240
. The Teflon
®
also covers the bulb. The thermostat is
30 to 220˚F
DPST (Double Pole/Single Throw)
25 Amperes, 120 or 240 Vac
±9˚F
120 Vac or 240 Vac
GNIT-5, 5 Foot
GNIT-12, 12 Foot
Cover 5/16" OD
®
GNIT
SECTION
PK479-3
161-506172-001
Max
Capillary
Stock
Amps. Length (Ft.)
25
5
S
25
12
S