Chromalox WCRT-100 Installations- und Betriebsanleitung

Blättern Sie online oder laden Sie pdf Installations- und Betriebsanleitung für Thermostat Chromalox WCRT-100 herunter. Chromalox WCRT-100 4 Seiten. Weather-corrosion resistant room thermostat

Type WCRT thermostats are intended for use in harsh environ-
ments. They tolerate continuous spraying with water, high humid-
ity, airborne contaminates and moderately corrosive conditions.
The nickel plated sensing bulb is attached directly to the bottom of
the case where it is shielded from damage or accumulations of
insulating particles. The molded Noryl case is sealed at the cover
with a neoprene gasket and the adjusting knob opening is closed
with a lubricated O ring. Underwriters Laboratories has tested the
WCRT and found it meets the requirement for NEMA 4X areas.
High levels of accuracy and sensitivity, 2
vided by the WCRT. Switching is done by heavy duty, precision,
single stage, SPDT line voltage snap action switch. Setting is
accomplished by rotating the adjusting knob. The dial face is print-
ed with large, contrasting numbers and letters on a lustrous back-
ground for good visibility. Color coding clearly identifies the func-
tion of each conductor.
Applications – Automatically controls room temperature by turn-
ing electric air heaters on and off. Can be used to control the air
heaters directly, within thermostat rating. For higher ratings use
thermostat with magnetic contactor. Place thermostat on inside wall,
away from undue heating or cooling influences, about 4 feet above
the floor.
© 2010 Chromalox, Inc.
Installation
and
OPERATION INSTRUCTIONS
UL LISTED
Figure 1
1
/
° differential, are pro-
2
WCRT Weather-Corrosion
Resistant Room
Thermostat
Specifications – Table A
Temperature Switch
Model
Range (°F)
Action
WCRT-100
40-100
SPDT
GENERAL
NOTICE: Type WCRT thermostats are designed for temperature
control service only. Because they do not fail safe, they should
not be used for temperature limiting duty.
W W A A R R N N I I N N G G : : Users should install adequate back-up
controls and safety devices with their electric heat-
ing equipment. Where the consequences of failure
may be severe, back-up controls are essential.
Although the safety of the installation is the
responsibility of the user, Chromalox will be
glad to make equipment recommendations.
Principle of Operation – Control action of these thermostats is
provided through the principle of liquid volume change. With a
variation in temperature, the liquid in the sensing element expands
or contracts, causing a bellows to actuate the switching mechanism.
WARNING: Not for use in hazardous environments as
described in National Electrical Code. Failure to com-
ply can result in explosion or fire.
LO Setting is positive open (black to red) for heating loads and
is positive closed (black to blue) for cooling loads.
Note: It is not recommended to switch systems directly from heat-
ing to cooling and vice versa.
4
WCRT
(Supersedes PK471-3)
161-562767-001
DECEMBER, 1998
Maximum Rating
Description
120 Vac
Full Load Inductive
16.0A
Locked Rotor
80.0A
Non-Inductive
25.0A
Pilot Duty
125VA
PK471-4
240 Vac
277 Vac
12.0A
10.0A
60.0A
55.0A
25.0A
22.0A
125VA
125VA