LIGHTING AND OPERATING INSTRUCTIONS
1. STOP! Read the safety information above on this label.
2. The gas valve must be shutt off by putting the ON/OFF
switch to position "0". Wait five (5) minutes to clear out
any gas. If you smell gas, STOP! Follow "B" in the safety
information above. If you do not smell gas, go to the
next step.
3. This water heater is equipped with a safety pilot burner
and an automatic ignition control system.
4. Set the ON/OFF switch (flip down cover plate on frontal
panel strip) marked I/0 to the I position. In this position,
the water heater is ready to use.
5. If the red LED indicator light (visible through the
peephole in the front panel strip) is flashing, this is a
warning that the batteries are less than 1.2 Volts and
will need to be replaced within the next couple of weeks.
Plan to have two D type 1.5 volt long-life (Alkaline)
batteries available for replacement.
6. Turn the hot water faucet on the minimum flow rate
required to activate the heater. The automatic ignition
system first ignites the safety pilot burner which then
ignites the main burner in about 4 seconds.
7. The pilot flame will extinguish 10-30 seconds after the
burners come on. The burners will remain on until the
hot water tap is turned off.
NOTE: On a first time initial installation, existence of air in
the gas supply line and in the water line may cause some
ignition delay. In that case, repeatedly open and close the
hot water tap in order to restart the ignition process until
all the air has been purged.
TO TURN OFF GAS TO APPLIANCE
Turn off the manual lever on the gas supply line to the
heater and set the ON/OFF switch to the OFF ( 0 ) position.
SETTING THE WATER TEMPERATURE
The AquaStar 125 X LP and 125 X NG water heaters have
a gas control that modulates burner input in response to
flow. Its purpose is to ensure that the hot water temperature
will remain steady, although the water flow demand might
vary (down to 1/2 gal/minute). To adjust the temperature
on your AquaStar, turn on a hot water faucet to its
maximum flow. At the water heater, turn the large knob
located beneath the main gas control on the front of the
heater all the way to the right (clockwise). See Fig 8. This
will produce a temperature rise of approximately 90°F at
flow rates between 0.5 and 2.0 gallons per minute. Given
that average incoming water temperatures are 50°F, this
heater will produce approximately 140°F water at these
flow rates. Turning the dial all the way to the left
(counterclockwise) will produce a temperature rise of
approximately 45°F for flow rates between 1.1 and 3.7
gallons per minute. It is safest to select a comfortable
temperature and not have to mix in cold water.
Fig. 8 - Temperature Adjustment Knob
What is the best temperature setting? Because AquaStar
water heaters deliver endless hot water at the temperature
you have selected, there is no need to produce very hot
water and then mix in cold. It just does not make sense to
overheat water and then mix in cold to cool it off. You cannot
run out of hot water with an AquaStar, so set the dial for
the temperature you prefer . Note: 105 ° F is the maximum
recommended for a hot bath. The position you select on
the temperature adjustment knob will depend on the
temperature of the incoming water (50 ° F is average in the
U.S.). In warm weather regions where the incoming cold
water is generally warmer, or during the hot weather
months in some other areas a midway setting on the
temperature adjustment knob would produce a
temperature rise of about 70 ° F, giving an output of
approximately 120 ° F. At this setting, if it is still necessary,
one could mix a small amount of cold water in a shower
and have a comfortable shower at about 3 gallons/minute.
During the colder months, or in cold climate areas, it might
be necessary to set the control to the maximum position,
all the way clockwise to the right.
If you supply the AquaStar 125X, with preheated water
(i.e.) in a solar installation the unit could overheat. It will
then shut off on safety when the outlet temperature reaches
194 ° F. For this type of application, purchase a solar model
125B LPS or 125B NGS.
Align batteries as
If the LED light is flashing, prepare to
shown
replace the batteries. Use two D cell
(1.5 volt) long life alkaline batteries.
To operate the heater, set the ON/OFF switch to position I.
The switch is located behind the flip down cover plate on
the front panel strip.
To shut down the gas to the heater, set the ON/OFF switch
to position 0
Temperature Adjustment Knob
Decrease temperature
and increase flow
Fig. 9 - Principles of Operation
T E M P E R AT U R E
A D J U S T M E N T K N O B
Increases temperature
and decreases flow