ABB VD4 Series Gebrauchsanweisung - Seite 19
Blättern Sie online oder laden Sie pdf Gebrauchsanweisung für Industrielle Ausrüstung ABB VD4 Series herunter. ABB VD4 Series 20 Seiten. Vacuum circuit-breaker with embeded poles
4.4
Delivery
The duties of the consignee on receipt of
the switching devices at site include the following:
Checking the delivery for completeness
●
and freedom from damage (e.g. moisture
and itsadverse effects).
Any short quantities, defects or damage
●
intransit:
- Must be precisely documented on
the consignment note.
- The shipper/carrier is to be notified
immediately in accordance with the
l i a b i l i t y p r o v i s i o n s .
Note:
Always take photographs to document any major
damage.
4.5
Intermediate storage
Intermediate storage of the circuit-breaker unit
in the switch position OFF and the stored-
energy spring mechanisms discharged (Indicator
DISCHARGED:
Conditions for optimum intermediate storage:
1. Devices with basic packaging or unpacked:
A dry and well ventilated storeroom
●
with climate in accordance with GB/T 11022,
IEC 60694, DIN VDE 0670.
Room temperature which does not fall below
●
-15˚C.
Do not remove or damage the packaging.
●
Unpackaged devices:
●
- Are to be loosely covered with
protective sheeting.
- Sufficient air circulation must be
maintained.
Check regularly for any condensation.
●
2. Devices with seaworthy or similar packaging
with internal protective sheeting:
Store the transport units:
●
- protected from the weather,
- dry,
- safe from damage.
Check the packaging for damage.
●
Check the drying agent
●
- on arrival of the consignment,
- subsequently at appropriate intervals.
).
5
Installation
(Figures 3/4, 4/1 and 4/2)
Perfect operation of the circuit-breaker depends
on careful and professional handling of
the withdrawable part.
Allocate each unit to the appropriate switchgear
●
panel in accordance with the switchgear plan
and the rated electrical data.
Remove the transport profile 148 and transport
●
brackets 147.
Insert the withdrawable part in the switchgear
●
panel checking for unimpeded motion and
function sequences, including the closing
of primary contacts when the service position
is reached.
Remove any dirt.
●
When the switchgears are operated in areas
with high humidity and/or major rapid
temperature fluctuations, there is a risk of dew
deposits which must remain an exception in
normal operating conditions Provisions should
be taken according to section 1.3.2 (special
operating conditions).
19