ABB ControlMaster CMF Handbuch - Seite 12
Blättern Sie online oder laden Sie pdf Handbuch für Controller ABB ControlMaster CMF herunter. ABB ControlMaster CMF 16 Seiten. Fieldmount universal controller/indicator
7
Diagnostic messages
The controller (or indicator) is programmed to display diagnostic messages that provide information on servicing requirements and
any other conditions that develop during operation.
When a diagnostic condition is detected, the associated NAMUR icon, plus the highest priority diagnostic message, is displayed in
the Status Bar when in Operator View. A list of all currently active diagnostic alarm states are displayed in the Diagnostic View.
Diagnostic status bar / Diagnostic View
Diagnostic
status bar
*The Diagnostic View is selected via the Operator Level (see Section 4, key A) / View Select menu.
Diagnostic messages
Icon
Number / Message
242.004
ADC 1 Failed
240.005
ADC 2 Failed
250.000 (248.001)
PV 1 (2) Failed
246.002 (244.003)
RSP 1 (2) Failed
222.014 (220.015)
CJ 1 (2) Failed
226.012 (224.013)
DV 1 (2) Failed
230.010 (228.011)
WV 1 (2) Failed
234.008 (232.009)
PFB 1 (2) Failed
216.016
NV Error Proc Bd
12
Operator View
PV1 Failed
Failure
Maintenance
High Process Alarm
Low Process Alarm
Possible Cause
Temporary or permanent failure of analog to digital
converter on the main I/O board.
Temporary or permanent failure of analog to digital
converter on the option board.
Problem with Input assigned to Loop 1 (2) PV.
Broken sensor leads, defective input source or
input signal out of permitted range.
Problem with Input assigned to Loop 1 (2) Remote
Setpoint. Broken sensor leads, defective input
source or input signal out of permitted range.
Error in Cold junction measurement associated
with AIN1 (AIN3). Wiring fault or defective sensor.
Problem with input assigned to Loop 1 (2)
disturbance variable. Broken sensor leads,
defective input source or input signal out of
permitted range.
Problem with input assigned to Loop 1 (2) wild
variable. Broken sensor leads, defective input
source or input signal out of permitted range.
Problem with input assigned to Loop 1 (2) position
feedback. Broken sensor leads, defective input
source or input signal out of permitted range.
Failure of non-volatile memory on processor /
display board or permanent corruption of its data.
Diagnostic description /
alarm tag
NAMUR (NE107)
Status icons
Out of Spec
High Latch Alarm
Suggested Action
Cycle power to device.
If problem persists replace main I/O board, contact local service
organization.
Cycle power to device.
If problem persists replace option board, contact local service
organization.
Check wiring. Check input source.
Check if input signal is outside permitted limits.
Check wiring. Check input source.
Check if input signal is outside permitted limits.
Check cold junction device is correctly fitted.
Ensure I/P 2(4) is turned off. Replace CJ sensor.
Check wiring. Check input source.
Check if input signal is outside permitted limits.
Check wiring. Check input source.
Check if input signal is outside permitted limits.
Check wiring. Check input source.
Check if input signal is outside permitted limits.
Check all configuration parameters and correct any errors.
Acknowledge error.
If problem persists contact local service organization.
Diagnostic View*
Alarm
High High Alarm
icons
High Alarm
PV1 Failed
Check Function
Low Latch Alarm
CI/CMF160/310–EN Rev. C