Make-Up Air -
continued
Make-Up Air Set Point* Descriptors/Value Default Use
Min Speed Set
Max Speed Set*
Tempering Set*
Tempering Status
Fault Menu (No Settings)
Faults
System Fault
Fire
Temp Fail
Pressure Fail
Exh VFD Fault
MUA VFD Fault
Exhaust
Exhaust Fan Speed*
EF1 Speed
EF2 Speed
EF3 Speed
EF4 Speed
EF5 Speed
EF Min. Fan Speed*
EF1 Min
EF2 Min
EF3 Min
EF4 Min
EF5 Min
* To see values, you need to log in.
0-100%
50%
0-100%
100%
0-100%
66%
On / Off
Off
No/Yes
No
No/Yes
No
No/Yes
No
No/Yes
No
No/Yes
No
No/Yes
No
0-100%
-
0-100%
-
0-100%
-
0-100%
-
0-100%
-
0-100%
50%
0-100%
50%
0-100%
50%
0-100%
50%
0-100%
50%
The minimum output control limit for the MUA
VFD or damper. Must be set to a value that
ensures proper design full flow CFM (Adjustable
from 0% to 100%)
The maximum output control limit for the
MUA VFD or damper. Must be set to a value
that ensures proper design full flow CFM.
(Adjustable from 0% to 100%)
Minimum run percentage for the MUA when
heating or cooling is being used.
Displays whether the MUA is heating or cooling
Indicates that there is a fault due to the
following:
Status of contact input from fire alarm system.
Closed contact allows the fan to run.
Indicates that one of the temperature sensors
used to control the hood exhaust has failed.
Indicates that the pressure sensor has failed.
Status of exhaust fan VFD(s) fault contacts.
Open if failed.
Status of MUA fan VFD(s) fault contacts. Open
if failed.
Indicates the speed at which EF1 is running
Indicates the speed at which EF2 is running
Indicates the speed at which EF3 is running
Indicates the speed at which EF4 is running
Indicates the speed at which EF5 is running
Indicates the minimum fan speed to achieve
positive hood capture for EF1
Indicates the minimum fan speed to achieve
positive hood capture for EF2
Indicates the minimum fan speed to achieve
positive hood capture for EF3
Indicates the minimum fan speed to achieve
positive hood capture for EF4
Indicates the minimum fan speed to achieve
positive hood capture for EF5