Diginet DGEMSR360P1 Benutzer- und Installationshandbuch - Seite 6

Blättern Sie online oder laden Sie pdf Benutzer- und Installationshandbuch für Sicherheitssensoren Diginet DGEMSR360P1 herunter. Diginet DGEMSR360P1 16 Seiten. Recessed flush mount 360 pir presence sensor

DIGINET ENERGY MANAGEMENT
Figure 3 – DGEMSR360P2 electrical connections (ILSCM02-D two channel module).
5.2.

Override 'OFF'

The presence sensor has an override 'OFF' function that is activated by an external switch connected to the
control module. This function only operates Relay 1 for both one and two channel control modules. Relay 2 in the
two channel model will continue to operate under presence detection mode.
The override switch has two methods of connection: dry contact switch input across both terminals to make a
closed circuit or a switched active input. A latched contact/switch (not momentary/push button) must be used in
both methods. Refer to Figure 4 for the electrical connections of the two methods for operating the override
function.
Note: Terminals S1 and S2 require a consistent polarity if installing one or more switches to a single
or multiple control modules.
S 2
S 1
Figure 4 – Override 'OFF' switch connection options.
Diginet Control Systems Pty Ltd
R1
N
A/L
S 2
S 1
R2
Latched contact / switch
S 2
S 1
Dry contact
Recessed Flush Mount 360
Load 1
Switched Active
Active – any phase and/or circuit
Neutral
Active
See Section 5.2 for override
switch connections
Active – any phase and/or circuit
Switched Active
Load 2
n/c
(same circuit as A/L)
o
PIR Presence Sensor
Neutral
Neutral
Active
Page 6 of 16