Accustat Independence ES-U Betriebsanleitung

Blättern Sie online oder laden Sie pdf Betriebsanleitung für Thermostat Accustat Independence ES-U herunter. Accustat Independence ES-U 3 Seiten.

Installation and Operating Instructions
ES-AH11
Environmentally Friendly
MERCURY FREE!!
Use ONLY ACCUSTAT®
Temperature Setpoints
Application:
The ACCUSTAT®
designed to operate 24VAC to 30VAC single stage heating and cooling
systems. This thermostat is MERCURY FREE!! The ACCUSTAT®
models utilize pre-set plug-in temperature setpoints to
activate the circuits. Room air temperature is measured by a micro-
processor and compared with the plug-in setpoint temperature. This
thermostat can operate in heat only, cool only or be off. The fan cycles
on/off with calls for heating or cooling or can be on continuously. The
thermostat has a locking cover to prevent tampering.
Operating Conditions:
The electronic mechanisms incorporated within this unit REQUIRE
operating conditions similar to other electronic devices intended for
INDOOR USE ONLY, such as would be acceptable for TV and similar
household appliances. Relative humidity must be less than 95% and
the atmosphere must be non-condensing. Air quality must be main-
tained, FREE of heavy dust or debris which may infiltrate the interior
of this device. Installation in any space which is unfinished or under-
going repainting or general rehabilitation is also considered product
abuse. This device should be removed from service during any local
construction activity.
Cleaning:
This device incorporates a high impact styrene enclosure which is
easily cleaned with a dry cloth or vacuum brush. Occasional soiling
may be cleaned with a soft cloth lightly dampened with water and/or
mild cleaning solution. IN NO CASE should this device be directly
sprayed with or exposed to free flowing liquids, including water, which
could penetrate its interior.
FAILURE TO OBSERVE ANY OF THE ABOVE CONDITIONS OF USE
WILL COMPLETELY VOID THE SUPPLIER WARRANTY.
CAUTION
MAKE SURE UNIT IS PROPERLY CONNECTED. DAMAGE TO THE
CONTROL CAN BE CAUSED BY MISWIRING, WHICH WILL VOID
THE WARRANTY.
FAN
ON AUTO
ACCUSTAT
HEAT OFF COOL
model ES-AH11 thermostat was
Specifications:
Set Temperature Range: Determined by plug-in setpoint
Plug-in Setpoint Accuracy: ± 0.5°
Control Accuracy: ± 1.0°
Sampling Rate: Every 30 seconds
System: Switch selectable, heat only, cool only or off
Stages: Single stage heating/cooling
Differential: Switch selectable, 0.5° or 1.0°
Fan: Switch selectable, auto cycle or continuously on
Operating Temperature: 14°F to 105°F
Storage Temperature: -4°F to 105°F
Input: 20VAC to 32VAC
Load Rating: 1 amp maximum per circuit, 80mA minimum for
energy harvesting
Cycle Rate: 6 cycles per hour
Common Wire: Optional
Delay: 5 minutes on start-up
Energy Harvesting: Switch selectable, on or off
Enable switch if not connecting a common wire
Disable switch for sensitive loads, common wire will then be required
Thermostat Charge: Thermostat will hold its charge 3.5 hours during
a power failure
Enclosure: High impact styrene, white
Case can be locked, key required
TO OPEN:
1. Align key with slot and insert all the way
2. Locking pin will emerge. Pull out completely
3. Gently squeeze left side of cover to
release catches
4. Let right side work as a hinge
Swing cover out and remove
3
Squeeze
1
Insert
TO CLOSE: (Reverse Procedure)
1. Hinge right side of cover and close it
2. Gently squeeze left side of cover and
snap shut
3. Orient the locking pin as shown and
slide in until end is below surface of
cover (audible snap is heard when
pin is properly seated)
ATTENTION: This product does not contain mercury.
This product may be replacing a product containing
mercury.
Do not place the old product in the household trash.
For more information on recycling and proper disposal
visit TRC's website www.thermostat-recycle.org
Should a tube break, do not touch any spilled mercury.
Wear non-absorbent gloves, collect any spilled mercury
and place it in a sealed container. Contact your local waste
management authority for recycling and proper disposal
instructions.
1
Lift and
2
4
Rotate
Remove