Crestron CH-HREL8-D6 Betriebshandbuch - Seite 3
Blättern Sie online oder laden Sie pdf Betriebshandbuch für Controller Crestron CH-HREL8-D6 herunter. Crestron CH-HREL8-D6 12 Seiten. Electrical control interface (din rail)
CH-HREL8-D6
Description
Functional Description
The CH-HREL8-D6 is a Cresnet relay interface (Figure 1).
• 8 single pole single throw high voltage relays.
• Each relay can handle 16Amp at 250V and is protected with a VDR (385 Volts).
• Red LED feedback per relay + manual override per relay with dip switches.
• Interface connects directly to Cresnet. Two 4-pole Phoenix connectors on board for
easy daisy-chaining of multiple interfaces. Cresnet addressing through software.
• DIN rail mountable universal casing to fit in any standard electrical cabinet. Takes 6
DIN modules in the cabinet.
Usage
Typical applications
!!! IMPORTANT!!!
Do NOT use the CH-HREL8-D6 for MOTOR control or other inductive loads.
Use the CH-HMOT2-D9 for these types of applications.
Crestron International • 2 Oude Keerbergsebaan • 2820 Rijmenam • Belgium
Tel: +32 15 50 99 50 • [email protected] •
Figure 1: CH-HREL8-D6
:
Light switching
HVAC control
DIA – FILM projectors
A/V power control
....
www.crestron-int.be
Product Manual