Auch für Siemens SIMATIC ET 200SP HA: Handbuch (32 seiten), Handbuch (50 seiten), Handbuch (34 seiten), Handbuch (38 seiten), Handbuch Ausrüstung (44 seiten), Handbuch Ausrüstung (38 seiten), Handbuch Ausrüstung (46 seiten), Handbuch Ausrüstung (42 seiten), Handbuch Ausrüstung (44 seiten), Handbuch Ausrüstung (36 seiten), Handbuch Ausrüstung (38 seiten)

Siemens SIMATIC ET 200SP HA Handbuch Ausrüstung
Principle of change-over contact diagnostics
If the digital inputs of a channel group are configured as "change-over contacts", the module for
this channel group carries out diagnostics for the change-over contact encoder type.
If the plausibility check is negative, the following happens:
• The module identifies the value status of the NO channel as "invalid" (QI = "0").
• The module creates a diagnostics entry for the NO channel.
• If the change-over contact error diagnostics is enabled, a diagnostic interrupt is triggered.
The digital input signal and the value status are only updated for the NO channel. The digital
input signal is 0 and the value status is "invalid" (QI = "0") for the NC channel. This channel is only
used for a validity check of the sensor.
Special features
Please note the following special features for change-over contact diagnostics:
• If the normally open and normally closed contact signals are not plausible after 300 ms, a
change-over error is output as diagnostics information.
• If there is already a fault (QI = 0, e.g. a wire break), the module will no longer perform
diagnostics for change-over errors.
• There are different diagnostics options depending on the type of change-over contact.
Depending on the encoder type, a change-over error can have different causes.
– In the case of connected change-over contacts, a change-over error may also be the result
– In the case of unconnected change-over contacts, a change-over error may also be the
– If a wire break or short-circuit can be detected with the particular encoder type but its
DI 16xNAMUR HA
Equipment Manual, 08/2019, A5E39293880-AD
7.4 Useful information about diagnostics for the change-over contact encoder type
of a short-circuit (encoder is not defective; there is a short-circuit).
result of a wire break.
diagnostics is not enabled, instead of the wire break or short-circuit diagnostics
information, the change-over error diagnostics information is displayed if this is enabled.
Displays and interrupts