Address space
4.1
Address space
The module can be configured in various ways in STEP 7. Depending on the configuration,
additional/different addresses are assigned in the process image of the inputs.
Configuration options of DI 16x24VDC BA
You can configure the module with STEP 7 (TIA Portal) or with a GSD file.
When you configure the module by means of the GSD file, the configurations are available
under different abbreviations/module names.
The following configurations are possible:
Table 4- 1
Configuration options
Configuration
1 x 16-channel without value status
2 x 8-channel without value status
1 x 16-channel with value status for
module-internal Shared Input with up
to 4 submodules
Digital input module DI 16x24VDC BA (6ES7521-1BH10-0AA0)
Manual, 09/2014, A5E32363114-AB
Short designation/
module name in the GSD file
DI 16x24VDC BA
DI 16x24VDC BA S
DI 16x24VDC BA MSI
Configuration software, e.g., with STEP 7 (TIA
Portal)
Integrated in hardware
catalog
STEP 7 (TIA Portal)
V13 or higher
V13 Update 3 or higher
(PROFINET IO only)
V13 Update 3 or higher
(PROFINET IO only)
4
GSD file in STEP 7
(TIA Portal) V12 or
higher or STEP 7
V5.5 SP3 or higher
X
X
(PROFINET IO only)
X
(PROFINET IO only)