Auch für Siemens SINAMICS G120P: Betriebsanleitung (28 seiten), Betriebsanleitung (26 seiten), Betriebsanleitung (24 seiten), Betriebsanleitung (22 seiten), Betriebsanleitung (26 seiten), Betriebsanleitung (22 seiten), Betriebsanleitung (22 seiten), Handbuch (18 seiten), Betriebsanleitung (18 seiten)

Siemens SINAMICS G120P Betriebsanleitung

General

Description
The du/dt filter compact plus Voltage Peak Limiter comprises two components: the du/dt
reactor and the voltage-limiting network (Voltage Peak Limiter), which cuts off the voltage
peaks and feeds back the energy into the DC link. The du/dt filter compact plus Voltage
Peak Limiter is designed for use with motors for which the voltage strength of the insulation
system is unknown or insufficient.
du/dt filters compact plus Voltage Peak Limiters limit the voltage rate of rise du/dt to values <
1600 V/µs - and the typical voltage peaks to the following values according to limit value
curve A acc. to IEC 60034-25:2007:
● < 1150 V at U
● < 1400 V at 660 V < U
Fire hazard due to overheating because of inadequate ventilation clearances
Inadequate ventilation clearances can cause overheating with a risk for personnel through
smoke development and fire. This can also result in increased failures and reduced service
lives of braking resistors.
• Maintain 100 mm ventilation clearances above and below the component.
• Always mount the du/dt filters compact plus Voltage Peak Limiter in a vertical, upright
Risk of burns due to high surface temperature of the du/dt filter compact
The surface temperature of the dv/dt filters compact may exceed 80 °C. You can get
seriously burnt when touching the surface.
• Mount the du/dt filters compact so that they cannot be touched. If this is not possible,
dV/dt filter compact plus Voltage Peak Limiter
Operating Instructions, 04/2016, A5E32847614B AC
< 575 V
line
line
WARNING
position, to enable cooling air to flow through the heat sink on the Voltage Peak Limiter
from the bottom to the top.
CAUTION
attach a clearly visible and understandable warning notice at hazardous positions.
< 690 V.
2
11