Siemens SQM56.564R1G4 Technische Anweisungen - Seite 21
Blättern Sie online oder laden Sie pdf Technische Anweisungen für Controller Siemens SQM56.564R1G4 herunter. Siemens SQM56.564R1G4 31 Seiten. Reversing
Auch für Siemens SQM56.564R1G4: Technische Anweisungen (31 seiten), Technische Anweisungen (31 seiten)
SQM5... Reversing Actuators
AGA56.41/42/43
Circuit Board
Installation,
Continued
Siemens Building Technologies, Inc.
Re-install the actuator motor capacitor.
See Figure 20.
Gently guide the terminal section into the
support slots and slide the terminal
board downward until both supports
snap into place. Ensure that the four
brown wires and the flat white
connector cable which connect the two
circuit boards are positioned correctly
in their respective corners allowing the
board to freely slide into place without
pinching either wire. See Figure 21.
Connect the bundled blue, black and
brown potentiometer wires to the
terminal block located on the ASZ...
potentiometer circuit board. See
Potentiometer Installation.
Technical Instructions
Document No. 155-517P25
Mar 3, 2021
Figure 20.
Figure 21.
Page 21