Siemens TL-30U Einbauanleitung - Seite 2
Blättern Sie online oder laden Sie pdf Einbauanleitung für Kontrolleinheit Siemens TL-30U herunter. Siemens TL-30U 2 Seiten. Time limit module
Typical Wiring
Programming the TL-30U
There are two jumpers and one potentiometer on the
component board used to program the module.
TIME IN/TIME OUT JUMPER*
T0
COM.
TI
Determines whether TL-30U will be
time in or time out. Connect jumper
between common and T0 or TI.
*Time in denotes delay time period before
terminal 3 goes high (+).
Adjust potentiometer R13 (500K) for the exact time
period desired. Cross-zoning may be accomplished
without the use of zone operated relays. The two zone
outputs are fed directly into the TL-30U (terminals 1
and 2). After the second zone has activated, the TL-30U
will time as programmed.
NOTES
1. Jumper terminal 2 to terminal 1.
2. All input/output signals not supervised.
3. Minimum wire size: 18 AWG
Maximum wire size: 12 AWG
4. Terminals 1-6 are power limited.
P/N 315-021315-10
LONG TIME/SHORT TIME JUMPER
LT
COM.
ST
Determines timing period. LT: 30 sec
-10 min, ST: 1-20 sec. Connect
jumper between common and LT or ST.