Siemens 15-FSV-750 Installation, Betrieb und Wartung - Seite 24

Blättern Sie online oder laden Sie pdf Installation, Betrieb und Wartung für Schalter Siemens 15-FSV-750 herunter. Siemens 15-FSV-750 48 Seiten. Vacuum circuit breakers fsv series and msv series

Siemens 15-FSV-750 Installation, Betrieb und Wartung
Interrupter/Operator
Description

Elementary Diagram

I
•.t,; �
'
- -
-
"
_
-
Figure 15.
Typical Elementary Diagram

Manual Closing

Press the close butto n , (53) The close-open indicator, (58 ) ,
will then display "closed" a n d t h e closing spring condition in­
dicator will now read " D I SCHARGED".

Manual Opening

The tripping spring is charged during closin g .
To open the breaker, p ress t h e trip button , (54) , a n d "OPEN"
wi l l be displayed by indicator, (58)
-
I I
- J. -
- , - c
I
7C
XIC7
...
kiD7
70
I
I
-L
Indirect Releases (Dual Trip and
Undervoltage)
The ind i rect release provides for the conversion of modest
control signals into powerful mechanical energy impulses . It is
primarily used to trip high voltage c i rcuit breakers while func­
tioning as a secondary (dual trip) release or undervoltage re­
lease device.
These releases are mechanical energy storage devices. Their
internal springs are charged as a consequence of the b reak­
ers mechanism operatin g , and are released upon application
or removal of applicable control voltages.
Refer to Figures 16, 16a, 16b, & 16c
-SYMBOL LIST-
Spring Charging Motor
88
Spring Release Coil (Close)
52SRC
52Y
Closing Relay (Anti-Pump)
52T
Shunt Trip Coil
LS
Spring Charged Switch
52a
Aux. Sw-Open When Brk is Open
52b
Aux Sw-Ciosed When Brk i s Open
R
Red lndicatong Light (Close)
_ ... _ . .
• T - y
G
Green indicating Light (Trip)
I
White indicating Light (Spnngs
W
Charged)
01/C
Control Switch (Close)
Control Switch (Trip)
01/T
Ml
Mechanical Interlock
I,
Note Shown as typical For actual control
schematic see contract drawings Devices
and wires shown dashed are external to the
breaker
. .
T
L
Page 19
1 8-806-54 1 -4
11
MSV/FSV