Permissible Conductor Size: Main Terminals
Termination Data - Contactor
Solid
Flexible without end sleeve
Flexible with end sleeve
Screw Size
Tightening Torque
B. Installation
1. Permitted mounting positions are indicated in Fig.2
2. The unit is suitable for screw mounting on flat vertical
surface with two M4 screws. Always use plain and spring
washers.
3. Alternatively snap for 3TS11.. to 3TS15.. on to a 35 mm
Top hat Rail TH 35 as per DIN : EN60715.
Note: Install the unit in housing if it is exposed to dust, dirt,
contamination or aggressive atmosphere.
Fig. 2 Mounting Positions for 3TS11... to 3T15...
E. Overall Dimensions
Dimensional drawing: 7/12.5,16, 20, 25 kVAr (3TS11/12/13/14/15..-0A .. 5-8K)
Siemens product are environment friendly, which predominantly
consist of recyclable materials.
For disposals we recommend disassembling and separation into
following materials:
METALS: Segregate into Ferrous & Non Ferrous types for recycling
through authorised dealer.
Customer Care Toll free no. 1800 220 987
Siemens Ltd.
SGR-02IO-813
Cable
3TS11 .. -0A .. 5-8K 3TS1200-0A .. 5-8K 3TS1300-0A .. 5-8K 3TS1400-0A .. 5-8K 3TS1500-0A .. 5-8K
mm
2
1 x (1 to 2.5)
mm
2
mm
2
1 x (0.75 to 2.5)
M3.5
N-m
0.8 to 1.4
Product development is a continuous process. Consequently
the data indicated in this Leaflet is subject to change without
prior notice. For latest issue contact our sales offices.
1 x (2.5 to 6)
1 to 16
1.5 to 16
1 x (1.5 to 4)
1.5 to 16
1.0 to 1.5
C. Maintenance
• Remove dust by suction.
• Replacement of coil available as spare.
• Spare contact kits available from 3TS12 to 3TS15.
• Contact Siemens Sales office for details.
• Handle the resistor wires carefully.
D. Note:
Normally the power factor controller in APFC panels, has the
provision for adjustment under voltage cut out with respect
to voltage and time. Please ensure that the controllers are
present as per values given in the table on right side.
Coil Voltage
Under Voltage setting Actuating time
110V
230V
415V
220-230V
400-415V
In case, Power factor controller does not have the provision
of above settings, it is recommended to provide a separate
undervoltage monitor having settings as per table, to ensure
satisfactory performance of the contactors. For further details
on such an undervoltage monitor, please contact nearest
Siemens office.
Type
A
B
C
3TS11
125
74
60
10
3TS12
136
85
70
14.5 115
3TS13..15 148
85
63
18
Disposal
PLASTICS: Segregate as per material type for recycling through
authorised dealer. Because of the long lifetime of Siemens
products the disposal guidelines may be replaced by other national
regulations when taking the product out of service.
The local customer care service is available at any time to answer
disposal-related questions
1 to 16
1.5 to 16
1.5 to 16
M4
2.5 to 3
Controller settings
≥ 94 V
≥ 196 V
≥ 353V
≥ 187V
≥ 340V
D
F
G
H
J
K
Ø E
115
78
45
60
35
4.8
85
45
75
35
4.8
120 103
55
75
45
5
Order No. A5E03830809000A
SACHIN ENTERPRISE
1 to 16
1.5 to 16
1.5 to 16
< 0.1 sec
< 0.1 sec
< 0.1 sec
< 0.1 sec
< 0.1 sec
Term
M
Screw
48
M3.5
51
M4
62.5
M4