Siemens SITRANS LVL200E Betriebsanleitung - Seite 22
Blättern Sie online oder laden Sie pdf Betriebsanleitung für Schalter Siemens SITRANS LVL200E herunter. Siemens SITRANS LVL200E 44 Seiten. Vibrating switches
Auch für Siemens SITRANS LVL200E: Gebrauchsanweisung (40 seiten), Betriebsanleitung (16 seiten), Betriebsanleitung (40 seiten)
Function/Configuration
22
6
Setup
6.1
General information
The figures in brackets refer to the following illustrations.
With plastic housings, the switching condition of the electronics can
be checked when the housing cover is closed (control lamp). With the
basic setting, products with a density ≥ 0.7 g/cm³ (0.025 lbs/in³) can
be detected. For products with lower density, the switch must be set
to ≥ 0.5 g/cm³ (0.018 lbs/in³).
On the electronics module you will find the following display and
adjustment elements:
•
Signal lamp (1)
•
DIL switch for adjustment of the density range (2)
Mode adjustment (A/B)
On the signal conditioning instrument SITRANS SCSC, SITRANS
TCSC, via the signal conditioning instrument.
The switching condition can be changed with the A/B switch. You can
set the required mode according to the "Function table" (A - max. de-
tection or overfill protection, B - min. detection or dry run protection).
The switching delay can also be modified on the signal conditioning
instrument (SITRANS SCSC, SITRANS TCSC signal conditioning
instruments).
Note:
Always immerse the tuning fork of SITRANS LVL200E in a liquid to
test its function. Do not test the function of SITRANS LVL200E with
your hand. This can damage the sensor.
6.2
Adjustment elements
Fig. 14: Oscillator SWE60Z - two-wire output
1
Control lamp (LED)
2
DIL switch for adjustment of the density range
SITRANS LVL200E - Operating Instructions
1
2
MAN-100411