6. Technical data

Description
Supply voltage
Max media temperature
Lock-out
Wires in cable
Compressor-start signal input
Permitted ambient temperature
Relative humidity
Relay
Fuse required
Enclosure class
Mounting of the detection circuit
Reset of lock-out state
Cable length
Weight
Dimensions
UL file number
Page 10
OLC-D1
115 VAC; ±10%, 50/60 Hz, 3VA /
230 VAC; ±10%, 50/60 Hz, 3VA /
24 VAC/VDC, ±10%, 50/60 Hz, 3VA
+120°C
Failure
5
No
Operation: -30°C – +60°C
Storage: -30°C – +80°C
Max. 95%RH non-condensing. Circuit board is
coated
Switch voltage 240 VAC, min 24 VAC
Continuous current max 2.5A, min 20mA
Switching capacity 300 VA,
C300 (pilot type use according to UL508)
Max 4A, fast-blow
Housing IP54; cable outlet pointing downwards
Screw mounted, M24
Max. tightening torque: 10 Nm by hand only
Interrupt supply power for min. 5 seconds
2050 ±50 mm
252 g
55.5 mm (w) x 87.0 mm (d) x 57.5 mm (h)
E348183
OLC-K1
115 VAC; ±10%, 50/60 Hz, 3VA /
230 VAC; ±10%, 50/60 Hz, 3VA
+100°C
Failure
Low oil level
6
Yes; violet wire
950 ±50 mm
152 g