CONDENSATE AND SAFETY TRAY DRAINAGE INSTRUCTIONS
SUGGESTED MINIMUM SLOPE TO ENSURE CORRECT DRAINAGE
25MM
CLEAR
PLASTIC
INSPECTION
TUBE
P-TRAP
INTERNAL CONDENSATE TRAY
SUGGESTED P-TRAP CONNECTION WITH LIMITED HEIGHT CLEARANCE
SUGGESTED P-TRAP CONNECTION WITH LONG DRAIN RUNS
NOTES:
1. REFER TO UNIT DIMENSIONS PAGE OF THE TECHNICAL CATALOGUE FOR SPECIFICATIONS OF DRAIN CONNECTORS.
2. TEST CONDENSATE DRAIN INSTALLATION TO ENSURE THAT WATER FLOWS FREELY AND DOES NOT LEAK. ALSO CHECK
THAT THE DRAIN TRAY DOES NOT OVERFLOW.
Page 10 of 20
CLAMP
BANDS
P.V.C
ELBOW
P.V.C
ELBOW
RETURN AIR
INDOOR COIL
INDOOR COIL
SUPPLY AIR
DESIGNS AND SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
REVISION DATE
05 - 05 - 2010
PREFERRED METHOD
OF CONNECTING P-TRAP
ENSURE DRAIN PIPES
SLOPE DOWN FROM THE
FAN COIL AT A MINIMUM
OF 10MM PER METRE
CONDENSATE DRAIN
CONNECTION
CONDENSATE DRAIN MUST BE
RUN SEPERATLY FROM THE
SAFETY TRAY DRAIN
SAFETY TRAY DRAIN
CONNECTION
THE TOP OF THE P-TRAP
MUST BE 50MM BELOW THE
TOP OF THE CONDENSATE
DRAIN CONNECTION
THE TOP OF THE P-TRAP
MUST BE 50MM BELOW THE
TOP OF THE CONDENSATE
DRAIN CONNECTION
Installation & Commissioning Guide - ESP Platinum ID Split Ducted Units
CONDENSATE AND SAFETY TRAY
DRAINAGE
DRAWING NUMBER
DFDRAIN - 100505
SEAL WITH
SILICONE
SEALANT
INSTALL A T-PIECE AS AN
AIR VENT FOR LONG DRAIN RUNS.
Doc. Part No. 0525-052 Rev. 5 200928
15MM